CV3100 series and MINI series high performance general purpose inverter instruction manual
6-12
Function of key
REV/JOG
on operating keypad can be set by this parameter, which
detailed setting as following:
0
:
This key is for REV running.
1
:
This key is for JOG running.
6.2 Motor and vector control parameter
P1.00
Motor rated voltage
Factory setting
380V/220V
Setting range
200V—500V/100V—250V
P1.01
Motor rated current
Factory setting
Determined by
inverter type
Setting range
0.1—600.0A
P1.02
Motor rated rotation speed
Factory setting
Determined by
inverter type
Setting range
300—3000RPM
P1.03
Motor rated frequency
Factory setting
50.00Hz
Setting range
1.00—400.00Hz
P1.04
Motor no-loading current
Factory setting
0.1A
Setting range
0.1—500.0A
The above parameters are for electric parameters of motor droved. If the power of
motor is different from the inverter, the difference must keep within two-level grade,
and the value of P1.01 must be same as the rated current of motor in order to ensure
correct parameters checkout of motor when in motor auto tuning.
P1.05
Motor stator resistance
Factory setting
Determined by
inverter type
Setting range
0.001—10.000Ω
P1.06
Motor rotor resistance
Factory setting
Determined by
inverter type
Setting range
0.001—10.000Ω
P1.07
Inductance of stator and
rotor
Factory setting
Determined by
inverter type