CV3100 series and MINI series high performance general purpose inverter instruction manual
6-5
When frequency setting channel is defined as digit setting(P0.01=1
、
2
、
3), the Initial
operating frequency is determined by this parameter. When operation keypad is under
monitoring mode, if set P0.01=1
,
then pressing ▲/▼ key can change the parameter
directly; If set P0.01=2
,
the inverter will first speed up to initial frequency, second its
output frequency increases or decrease based on the close or open status of
UP/DOWN terminal.
P0.04
Running command selection
Factory setting
0
Setting range
0 Operation commandof the digital keypad
1 Operation commandof the external terminal
2 Operation command of Communication interface
This parameter define inverter physical channel which receive the command of
operation ,stop,etc.
0
:
Operation command by the digital keypad
Operation by keys such as
RUN
、
STOP/RESET
、
REV/JOG
etc. on the keypad to
control the running command. Under this mode, external terminal FWD status will
influence the output phase sequence of inverter. When terminal FWD and COM are
connected together, the output phase sequence will reverse to the original setting; On
the contrary, when FWD and COM are disconnected.
1
:
Operation determined by the external terminal
Inverter running command is controlled by the on-off status of external terminal
FWD
,
REV and COM, of which control methods are determined by P4.06. Factory
setting as below:
Command
Terminal Status
Stop
FWD, REV and COM disconnection at the same time
Forward
FWD and COM close, REV and COM open
Reverse
REV and COM close, FWD and COM open
Table 6-2