5.6.4
Overview screen - System overview
Fig. 61 System overview
Status of emergency stop switch
Displays the corresponding status of the emergency stop
button on the system and the remote control.
Temperatures
Measured values of the corresponding temperature
sensors in °C
•
Ceiling:
Measured value of temperature sensor
underneath the ceiling
Warning b500 °C and +650 °C
Alarm from +650 °C
•
1m r/l:
Measured value of temperature sensor at 1 m height
Warning b200 °C and +250 °C
Alarm from +250 °C
Gas detector
Measured values of the respective gas detectors in %
LEL (lower explosive limit)
•
GasTR:
Measured value for gas detector
Warning between 15 % and 25 % LEL
Alarm from 25 % LEL