8.- INSTALLATION PRECAUTIONS
For the optimum operation of the machine it is advisable to follow these indications:
1)
Install the power unit as close as possible to the control unit. The connection ribbon cannot
exceed 20 cm in length.
2)
Avoid the routing of powered cables near the two units and the connection ribbon (if possible
shield the electronic part from the rest of the installation).
3)
Install the electromagnetic components as far as possible from the power unit.
4)
Install R-C groups (suppressors) of the suitable value in the electromagnetic components and
solenoid valves coils.
5)
The shielded cable of the temperature probe cannot be routed near other powered cables.
ENVIRONMENTAL CHARACTERISTICS
- Maximum relative humidity 90%, without condensation.
- Working temperature 0 °C ... +50 °C.
- Storage temperature -20 °C ... +63 °C.