Current Transformers
Recommended CT Phase Shift Values
Clamp On
CT-CON-0150EZ
CT-CON-1000
1.10°
0.20°
Split Core Small
CT-SCS-0050
CT-SCS-0100
2.20°
2.20°
Split Core
Medium
CT-SCM-0100
CT-SCM-0200
CT-SCM-0400
CT-SCM-0600
1.75°
1.50°
1.30°
1.30°
Split Core Large
CT-SCL-0600
CT-SCL-1000
0.00°
0.00°
Split Core High
Accuracy
CT
‐
SHS
‐
0005
CT
‐
SHS
‐
0015
0.50°
0.50°
Hinge Mini
CT-HSC-020
CT-HSAC-050
0.75°
0.75°
Hinge MIDI
CT-HMC-0100
CT-HMC-0200
0.12°
0.30°
Revenue Grade
Toroidal Solid
Core
CT-RGT12-0005
CT-RGT12-0020
CT-RGT12-0050
CT-RGT12-0100
0.00°
0.00°
0.00°
0.00°
Revenue Grade
Split Core
CT-SRS-005
CT-SRS-050
CT-SRL-100
CT-SRL-200
CT-SRL-400
-0.10°
-0.23°
0.06°
0.06°
-0.06°
Recommended CT Phase Shift Values
3) Click
OK
.
4) Check the
Enable THD
checkbox if you want total harmonic distortion to appear as a percentage in
the Data File Summary report. Selecting this option automatically populates any required value field
necessary to determine distortion.
Once the Quick Setup is completed, the
View Typical Setup
button appears in the Quick Setup area of
the screen. Clicking this button displays a wiring diagram showing how to connect the CTs and the
voltage leads of the
ELITE
pro
XC
corresponding to the selected setup. The diagram can be printed and
carried into the field for easy reference during installation. Refer to
ELOG Quick Setup Wiring Diagrams
for detailed information of each Quick Setup option.
www.
.com
1.800.561.8187
Содержание ELITEpro XC
Страница 58: ...58 Typical Single Phase 2 Wire Setup Diagram www com information itm com 1 800 561 8187 ...
Страница 59: ...59 Typical Single Phase 3 Wire Setup Diagram www com information itm com 1 800 561 8187 ...
Страница 60: ...60 Typical 3 Phase 3 Wire Delta Setup Diagram www com information itm com 1 800 561 8187 ...
Страница 61: ...61 Typical 3 Phase 4 Wire Wye Setup Diagram www com information itm com 1 800 561 8187 ...