42
D
ATA
L
OGGING
C
ONTROLS
The Data Logging section controls when the logger starts and stops collecting data. The default values
are
Start Immediately
and
Stop Never (Ring Memory)
. Additional data logging options are defined
below.
Start Options
Immediately
Logging starts as soon as the setup table is sent to the logger.
Date (mm/dd/yy)
Time (hh:mm:ss)
Logging starts at the designated date and time.
Time should be set in a 24-hour format, e.g., 2:30PM should be entered as
14:30.
Peak Demand Window
The default is 15 Minutes. Choices are Off, 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, and
60 minutes
.
Stop Options
Never (Ring Memory)
Logging is continuous, meaning when memory fills, the oldest records are
replaced with the newest records, allowing for long term metering projects.
When Memory Is Full
Logging stops when the memory is full.
Date (mm/dd/yy)
Time (hh:mm:ss)
Logging stops at the designated date and time.
Time should be set in a 24 hour format, e.g., 2:30 pm should be entered as
14:30.
M
EMORY
C
APACITY
ELOG provides a convenient feature that calculates the approximate length of time required to fill the
memory for any setup table. The feature is dynamic so that any time any parameter in a setup table
affecting the memory duration is changed, the Memory Capacity field is updated, providing the (new)
length of time the logger’s memory will last. The ELITEpro XC has 16 MB internal non-volatile memory.
www.
.com
1.800.561.8187
Содержание ELITEpro XC
Страница 58: ...58 Typical Single Phase 2 Wire Setup Diagram www com information itm com 1 800 561 8187 ...
Страница 59: ...59 Typical Single Phase 3 Wire Setup Diagram www com information itm com 1 800 561 8187 ...
Страница 60: ...60 Typical 3 Phase 3 Wire Delta Setup Diagram www com information itm com 1 800 561 8187 ...
Страница 61: ...61 Typical 3 Phase 4 Wire Wye Setup Diagram www com information itm com 1 800 561 8187 ...