25
Connecting R
ō
Coil CTs to a Load
1) Open the CT by squeezing the connector latch and pulling it apart.
2) Connect the CT around the load conductor to be measured. Orient the CT so that the arrow on the
CT case points towards the load. Make sure the maximum current of the conductor does not exceed
5,000 amps.
3) Push the connector back together with the conductor within the loop of the CT.
Repeat the above three steps if you are using more than one R
ō
Coil CT.
4) Connect the CTs brown wire to the negative terminal on the
connector. See photo below.
5) Connect the CTs white wire to the positive terminal on the
connector.
6) Twist together the bare shield wires from the R
ō
Coils and
connect to the “S” shield terminal that is part of the CH 4
connector. This reduces interference and improves accuracy
of the CT.
Connecting R
ō
Coil CTs to an ELITE
pro
XC
Shield Wires from DENT R
ō
Coil
CTs connected to ELITE
pro
XC
Negative
Positive
Shield