Environmental specifications
NOTE:
For additional information about environmental certifications, please refer to the Product Environmental
Datasheet located with the Manuals & Documents on
Table 24. Temperature specifications
Temperature
Specifications
Storage
-40–65°C (-40–149°F)
Continuous operation (for altitude less than 950 m
or 3117 ft)
10–30°C (50–86°F) with no direct sunlight on the equipment
Fresh air
For information about fresh air, see the
Standard operating temperature
section.
Maximum temperature gradient (operating and
storage)
20°C/h (36°F/h)
Table 25. Relative humidity specifications
Relative humidity
Specifications
Storage
5% to 95% RH with 33°C (91°F) maximum dew point.
Atmosphere must be noncondensing at all times.
Operating
10% to 80% RH with 29°C (84.2°F) maximum dew point.
Table 26. Maximum vibration specifications
Maximum vibration
Specifications
Operating
0.26 G
rms
at 5 Hz to 350 Hz (all operation orientations)
Storage
1.88 G
rms
at 10 Hz to 500 Hz for 15 minutes (all six sides tested)
Table 27. Maximum shock pulse specifications
Maximum shock pulse
Specifications
Operating
Six consecutively executed shock pulses in the positive and negative x, y, and z
axis of 6 G for up to 11 ms.
Storage
Six consecutively executed shock pulses in the positive and negative x, y, and z
axis (one pulse on each side of the system) of 71 G for up to 2 ms.
Table 28. Maximum altitude specifications
Maximum altitude
Specifications
Operating
3048 m (10,000 ft)
Storage
12,000 m (39,370 ft)
Table 29. Operating temperature derating specifications
Operating temperature derating
Specifications
Up to 30°C (86°F)
Maximum temperature is reduced by 1°C/300 m (1°F/547 ft), above 950 m
(3,117 ft).
30–40°C (86–104°F)
Maximum temperature is reduced by 1°C/175 m (1°F/319 ft), above 950 m (3,117
ft).
40–45°C (104–113°F)
Maximum temperature is reduced by 1°C/125 m (1°F/228 ft), above 950 m
(3,117 ft).
Technical specifications
145