Table 25. Particulate contamination specifications (continued)
Particulate contamination
Specifications
NOTE:
Air entering the data center must have MERV11 or
MERV13 filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive
particles.
NOTE:
This condition applies to data center and non-data center
environments.
Corrosive dust
•
Air must be free of corrosive dust.
•
Residual dust present in the air must have a deliquescent point less than
60% relative humidity.
NOTE:
This condition applies to data center and non-data center
environments.
Table 26. Gaseous contamination specifications
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013.
Silver coupon corrosion rate
<200 Å/month as defined by ANSI/ISA71.04-2013.
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Technical specifications
37