DKM-430 User Manual Rev_02                                                              Firmware V-1.8                     

 

 

 

K92D01-EN                                                 - 37 -                                              

 

The unit has 3 different password levels. Each password consists on a 4 digit number. 

 

 

 

When this menu is selected, the unit will ask for confirmation. 

Please adjust required selection with 

 and  

 buttons, then press 

 in order to return to 

PROGRAMMING section. 

 

 

 

Parameters adjusted in this section are used in the astronomical relay function. 

Parameter Definition 

Unit 

Min 

Max 

Factory 

Set 

Description 

TIME SOURCE 

RTC 

The unit picks up the date&time 
information only from the internal 
RTC. 

LOCATION SOURCE 

SET 

This parameter determines the source 
for geographical location information. 
The unit supports only manual entry. 

LATITUDE 

degrees 

66S 

66N 

41,000N 

This parameter defines the latitude as 
degrees.  

NOTE:

 Sunrise and sunset cannot be 

calculated for latitudes beyon polar 
circles. 

LONGITUDE 

degrees 

180W 

180E 

36,444E 

This parameter defines the longitude 
in degrees. 

TIME ZONE 

hour 

-12 

+12 

+2 

The effective time zone. For eastern 
longitudes the sign is positive. For 
wastern longitudes the sign is 
negative. Central Europe is generally 
+1 time zone. 
 

SUNRISE OFFSET 

minute 

 

 

30 

Defines the delay before sunrise that 
the astronomical relay will turn off. 

SUNSET OFFSET 

minute 

 

 

30 

Defines the delay after sunset that the 
astronomical relay will turn on. 

PLATE CODE 

100 

34 

Available for Turkey only. Latitudes 
and longitutes may be automatically 
selected from list. 

 

 

 

It is not possible to restore previous parameter settings. 

 

 

Passwords can only be modified at factory. 

 

11.14. LOCATION SETUP

 

11.13

. RETURN TO FACTORY SETTİNGS

 

11.12. CHANGE PASSWORD

 

Содержание DKM-430

Страница 1: ...elected from list Any function can be assigned to relay outputs of the unit Relays may be remotely operated through the central monitoring program The isolated RS 485 MODBUS RTU data port is unaffecte...

Страница 2: ...is required please contact the manufacturer directly at below e mail address datakom datakom com tr Please provide following information in order to get answers to any question Device model name see t...

Страница 3: ...k of malfunction or material damage ATTENTION Useful hints for the understanding of device operation The D 500 family units are available in various options and peripheral features Please use below in...

Страница 4: ...power before working on equipment When the unit is connected to the network do not touch terminals Short circuit terminals of unused current transformers Any electrical parameter applied to the device...

Страница 5: ...S 485 PORT 3 7 USB DEVICE PORT 3 8 GSM MODEM OPTIONAL 4 CONNECTION DIAGRAM 5 TECHNICAL SPECIFICATIONS 6 DESCRIPTION OF CONTROLS 6 1 FRONT PANEL FUNCTIONALITY 6 2 PUSHBUTTON FUNCTIONS 6 3 LED FUNCTIONS...

Страница 6: ...N TO FACTORY SETTINGS 11 14 LOCATION SETUP 12 INTERNAL RECORD MEMORY 13 CENTRAL MONITORING OF UNITS 14 E MAIL SENDING 15 SMS COMMANDS 16 MODBUS COMMUNICATIONS 16 1 PARAMETERS REQUIRED FOR RS 485 MODBU...

Страница 7: ...beyond specified range Voltage applied to digital inputs over specified range Current at measuring terminals beyond specified range Overload or short circuit at relay outputs Connecting or removing da...

Страница 8: ...e voltage inputs in close proximity of the unit Fuses must be of fast type FF with a maximum rating of 6A Use cables of appropriate temperature range Use adequate cable section at least 0 75mm2 AWG18...

Страница 9: ...0VAC all features active digital outputs open 60mA 110VDC all features active digital outputs open Measurement method True RMS Sampling rate 2048 Hz Harmonic analysis up to 17th harmonic Input voltage...

Страница 10: ...nimum Input impedance 1 ohm Burden 10 mW Maximum continuous current 500mA Measurement range 0 5 to 120mAA Display resolution 0 1A Accuracy 0 5 1 digit 100mA SELECTING THE CT ACCURACY CLASS The CT accu...

Страница 11: ...onnections are possible so check both order of CTs and their polarity Reactive power measurement is affected by incorrect CTs connection in similar way as active power measurement CORRECT CT CONNECTIO...

Страница 12: ...L1 100 0 0 0 100 1 00 Phase L2 100 0 0 0 100 1 00 Phase L3 100 0 0 0 100 1 00 Total 100 0 0 0 300 0 33 EFFECT OF PHASE SWAPPING The network is still loaded with 100 kW on each phase The load Power Fac...

Страница 13: ...olated Connection 3 wires A B GND Half duplex Baud rate 2400 115200 bauds selectable Data type 8 bit data no parity 1 bit stop Termination External 120 ohms required Common mode voltage 0 5 VDC to 7VD...

Страница 14: ...ftware programming control of the genset and monitoring of measured parameters are achieved The RainbowPlus software can be downloaded from www datakom com tr website The connector on the module is of...

Страница 15: ...only type SIM cards will usually not function properly Please refer to GSM Modem Configuration Guide for more details Description Quad band GSM GPRS 850 900 1800 1900MHz module GPRS multi slot class 1...

Страница 16: ...DKM 430 User Manual Rev_02 Firmware V 1 8 K92D01 EN 16 4 CONNECTION DIAGRAM...

Страница 17: ...Loading Voltage Input 0 02VA per phase Current Input 0 02VA per phase Relay Outputs 5A 250V AC Digital Inputs Active level 85 305VAC Min pulse 250ms Isolation 1000V AC 1 minute Serial Port Signal type...

Страница 18: ...oup Selects next display screen in the same display group When held pressed for 5 seconds enters PROGRAMMING mode 6 2 PUSHBUTTON FUNCTIONS 6 1 FRONT PANEL FUNCTIONALITY 6 DESCRIPTION OF CONTROLS Energ...

Страница 19: ...n the same group After the first display the last display comes again The list of parameter groups are below Channel Measurement Screens Voltage current kW kVA kVAr pf and reactive ratio of each input...

Страница 20: ...100 samples length and 13 bit resolution with a sampling rate of 2048 s s Thus one cycle of a a 50Hz signal is represented with 41 points The vertical scale is automatically adjusted in order to avoid...

Страница 21: ...024 samples length and 13 bits resolution with a sampling rate of 2048 s s The unit is able to analyze up to 900Hz and up to 17th harmonic whichever is smaller Alphanumeric Harmonics Table All harmoni...

Страница 22: ...ding on sunrise and sunset Astronomical relay display screen Astronomical relay parameter setting is performed through LOCATION SETUP group of the programming menu The date time information is picked...

Страница 23: ...occurring basis If an alarm is present following alarms will not be accepted Alarms may be of LATCHING type following programming For latching alarms even if the alarm condition is removed the alarms...

Страница 24: ...When the program mode is entered below password entry screen will be displayed A 4 digit password must be entered using buttons The buttons modify the value of the current digit The buttons navigate...

Страница 25: ...available parameters will be displayed Selected parameter is shown in reverse video black on white In order display change the value of this parameter please press button Parameter value may be incre...

Страница 26: ...lection keys If no button is pressed during 2 minutes the program mode will be cancelled automatically 10 3 MODIFYING PARAMETER VALUE 10 4 PROGRAMMING MODE EXIT Decrease parameter value Increase param...

Страница 27: ...is unlimited RS 485 Enable 0 1 1 0 RS 485 port disabled 1 RS 485 port enabled Modbus Address 0 240 1 This is the modbus controller identity used in Modbus communication RS 485 Baud Rate bps 2400 1152...

Страница 28: ...s not controlled Voltage Fail Timer sec 0 255 1 If the voltage goes outside limits during this timer a voltage alarm will occur Voltage Alarm Lock Enable 0 1 1 0 alarm non latching 1 latching alarm Fr...

Страница 29: ...tive Alarm 0 000 1 000 0 000 If the power factor of any channel is inductive and goes below this limit this will cause an alarm If this limit is 0 then the alarm is not controlled Power Factor Alarm D...

Страница 30: ...1 1 0 alarm non latching 1 latching alarm Voltage Unbalance Alarm 0 100 0 If the Voltage Unbalance goes above this limit this will cause an alarm If this limit is 0 then the alarm is not controlled V...

Страница 31: ...web page headers for the identification of the genset sending the message Any 20 character long string may be entered Serial Number The engine serial number string is designed to identify the current...

Страница 32: ...APN User Name The APN access point name username may be required by the GSM operator However some GSM operators may allow access without username The exact information should be obtained from the GSM...

Страница 33: ...functions Selected input name is displayed in the line below If this parameter is set to 0 then the input name string can be freely entered 0 User function 1 1 User function 2 2 Alarm Mute 3 High Temp...

Страница 34: ...gh kW alarm 19 kW alarm 20 kVAr Capacitive alarm 21 kVAr inductive alarm 22 kVAr alarm 23 Pf capacitive alarm 24 Pf inductive alarm 25 Pf alarm 26 High current alarm 27 THD V alarm 28 THD I alarm 29 T...

Страница 35: ...s 1 Please select character size with and buttons then press 2 Please select the value to display through SELECT AN ITEM menu then press For the next item to display the menu returns to the character...

Страница 36: ...o save the new calibration and return to PROGRAMMING section These parameters allow adjusting the battery backup real time clock of the module Once set the clock will continue to run even if supply po...

Страница 37: ...66N 41 000N This parameter defines the latitude as degrees NOTE Sunrise and sunset cannot be calculated for latitudes beyon polar circles LONGITUDE degrees 180W 180E 36 444E This parameter defines th...

Страница 38: ...RS 1 Activates the GPRS connection GPRS 0 Stops the GPRS connection RESET ALARMS Clears alarms of the controller The operating mode is not modified REBOOT Performs a hard reset on the controller no an...

Страница 39: ...k must use the same Baud Rate Selecting a higher baud rate will allow faster communication but will reduce the communication distance Selecting a lower baud rate will increase the communication distan...

Страница 40: ...Year 0 4095 8193 R W 32bit Month 1 12 8194 R W 32bit Date 1 31 8195 R W 32bit Day of Week 0 6 8196 R W 32bit Hours 0 23 8197 R W 32bit Minutes 0 59 8198 R W 32bit Seconds 0 59 ADDRESS decimal R W DAT...

Страница 41: ...12410 R W 32bit 1 Demand period 12416 R W 32bit 10 Input 01 current demand 12418 R W 32bit 10 Input 02 current demand R W 32bit 10 R W 32bit 10 12474 R W 32bit 10 Input 30 current demand 12476 R W 32...

Страница 42: ...e power kW 20612 R 32bit x100 Input 01 reactive power kVAr 20614 R 32bit x100 Input 02 reactive power kVAr R 32bit x100 R 32bit x100 20670 R 32bit x100 Input 30 reactive power kVAr 20672 R 32bit x100...

Страница 43: ...ent A 20875 R 16bit x1000 Analyzer 03 total reactive power ratio 20876 R 32bit x10 Analyzer 04 I1 current A 20891 R 16bit x1000 Analyzer 04 total reactive power ratio 20892 R 32bit x10 Analyzer 05 I1...

Страница 44: ...t x100 Harmonic 04 percentage 03 R 16bit x100 Harmonic 05 percentage 04 R 16bit x100 Harmonic 06 percentage 05 R 16bit x100 Harmonic 07 percentage 06 R 16bit x100 Harmonic 08 percentage 07 R 16bit x10...

Страница 45: ...0x0430 21831 R 16 bit Firmware version ADDRESS decimal R W DATA SIZE COEFF DESCRIPTION 22351 R 32 bit Bit_00 high voltage alarm Bit_01 low voltage alarm Bit_02 high frequency alarm Bit_03 low frequenc...

Страница 46: ...ive power alarm Bit_30 31 22361 R 32 bit Bit_00 Input 01 inductive cos alarm Bit_01 Input 02 inductive cos alarm Bit_02 Bit_03 Bit_29 Input 30 inductive cos alarm Bit_30 31 22363 R 32 bit Bit_00 Input...

Страница 47: ...lectronic equipment WEEE this unit should be stored and disposed separately from the usual waste The european ROHS directive restricts and prohibits the use of some chemical materials in electronic de...

Страница 48: ...eview chapter AC CURRENT INPUTS The unit is inoperative Measure the supply voltage between supply terminals Check that the unit s supply voltage is adequate to operating conditions If OK turn all fuse...

Отзывы: