DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 17 -
Supply Input:
85 - 305VAC, 50/60Hz,
88 - 450VDC
Optional 19-150VDC
Measurement Inputs:
Voltage:
7 - 300 V AC (P-N)
14 - 520 V AC (P-P)
Current:
0.001
– 0.12 A AC
Frequency:
45 - 65 Hz
Accuracy:
Voltage:
0.5% + 1 digit
Current:
0.5% + 1 digit
Frequency:
0.5% + 1 digit
Power
(kW,kVAr)
:
1.0% + 2 digit
Cos:
0.5% + 1 digit
Measurement Range:
CT range:
5A to 6500A
VT range:
1.0
/
1 to 5000.0
/
1
kW range:
1.0 kW to 5000 MW
Power Consumption:
< 6 VA
Loading:
Voltage Input:
< 0.02VA per phase
Current Input:
< 0.02VA per phase
Relay Outputs:
5A @ 250V AC
Digital Inputs:
Active level:
85
– 305VAC
Min pulse:
250ms.
Isolation:
1000V AC, 1 minute
Serial Port:
Signal type:
RS-485
Protocol:
Modbus RTU
Data Rate:
2400-115200b adjustable
İsolation:
1000V AC, 1 minute
Operating Temp. Range:
-
20°C to +70 °C (-4°F to 158°F)
Max Relative Humidity:
95%, non-condensing
Case Material:
Flame retardant, ROHS compliant, high temp. ABS/PC (UL94-V0)
Installation:
DIN rail or backpanel
Dimensions:
158x90x60mm (WxHxD)
Weight:
350 gr
AB Directives:
2006/95/EC (LVD)
2004/108/EC (EMC)
Reference Standards:
EN 61010 (safety)
EN 61326 (EMC)
5. TECHNICAL SPECIFICATIONS