DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 33 -
The unit has 2 digital inputs. Only parameters of one input are explained below. Other input have identical
parameter set.
The input name is freely programmable, thus the input can be adapted to any functionality through
programming.
Each digital input has below programmable parameters:
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Input Function
-
0
99
Selects between predefined input
functions. Selected input name is
displayed in the line below.
If this parameter is set to 0 then the
input name string can be freely entered.
0:
User function-1
1:
User function-2
2:
Alarm Mute
3:
High Temperature
4
: Panel Lock
Action
-
0
3
0:
alarm
Sampling
-
0
3
0:
always
Latching
-
0
1
0:
non-latching. The fault disappears
when cause is removed.
1:
latching. The fault persists even if the
cause is removed. Requires manual
reset.
Contact type
-
0
1
0:
Normally open
1:
Normally closed
Response delay
-
0.1
10
This is the delay between the fault
signal comes and the alarm occurs.
The input name entry is made through RainbowPlus
program only.
11.5. DIGITAL INPUT PARAMETERS