Measured analog values outside of programed limits cause an ALARM condition.
Alarms cause below, actions to be taken:
•
The
ALARM
led to turn on steadily,
•
The
Alarm
digital output to operate.
Alarms operate in a first occurring basis:
-If an alarm is present, following alarms will not be accepted,
Alarms may be of
LATCHING
type following programming. For latching alarms, even if the alarm condition is
removed, the alarms will stay on and disable the operation of the genset.
Most alarms have programmable trip levels. See the programming chapter for adjustable alarm limits.
If a fault condition occurs, the display will automatically
switch to the ALARM LIST page.
9. PROTECTIONS AND ALARMS