DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 8 -
Dimensions:
158x90x60mm (6.22
”x3.55”x2.36”)
Installation:
Panel base or DIN rail
Weight:
350g (0.77 lb)
Although the unit is protected against electromagnetic disturbance, excessive disturbance
can affect the operation, measurement precision and data communication quality.
▪
ALWAYS remove plug connectors when inserting wires with a screwdriver.
▪
Fuses must be connected to the power supply and phase voltage inputs, in close
proximity of the unit.
▪
Fuses must be of fast type (FF) with a maximum rating of 6A.
▪
Use cables of appropriate temperature range.
▪
Use adequate cable section, at least 0.75mm
2
(AWG18).
▪
Follow national rules for electrical installation.
▪
Current transformers must have 0.1A output.
2.1. DIMENSIONS
Current measurement is made with CTs provided together with
the module.
Do not apply direct connection, do not use 1A/5A current
transformers.
Do not install the unit close to high electromagnetic
noise emitting devices like contactors, high current
busbars, switchmode power supplies and the like.
2.2. ELECTRICAL INSTALLATION
2. MOUNTING