DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 27 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
LCD Contrast
-
30
50
39
This parameter is used to set LCD
contrast. Adjust for the best viewing
angle.
Language
-
0
1
0
0: English language selected.
1: Local language selected. This
language may depend on the country
where the unit is intended to be used.
Intermittent Alarm Timer
sec
0
250
60
If Intermittent Relay parameter is 1,
then the HORN relay is activated and
deactivated with this period.
Horn Timer
sec
0
120
60
This is the period during which the
HORN relay is active. If the period is set
to 0, this will mean that the period is
unlimited.
RS-485 Enable
-
0
1
1
0: RS-485 port disabled
1: RS-485 port enabled
Modbus Address
-
0
240
1
This is the modbus controller identity
used in Modbus communication.
RS-485 Baud Rate
bps
2400 115200
9600
This is the data rate of the RS-485
Modbus port.
Intermittent Alarm Relay
-
0
1
0
0: continuous
1: intermittent
LCD Backlight Delay
min
0
1440
60
If no button is pressed during this
period, then the unit will reduce the LCD
screen backlight intensity in for
economy.
Flashing Relay ON Timer
min
0
1200
0
Flashing relay ON state duration timer.
Flashing Relay OFF
Timer
min
0
1200
0
Flashing relay OFF state duration.
Internal Record Timer
sec
2
3600
900
Defines the data recording period to
internal memory. Shorter periods will
cause the internal memory to roll-up
more often.
11. PROGRAM PARAMETER LIST
11.1. CONTROLLER CONFIGURATION GROUP