DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 31 -
In this group, every current channel is adjusted independently and assigned to any analyzer unit.
A general CT ratio is provided for the ease of configuration. If the related channel’s CT parameter is left 0,
then the general CT ratio is used. Each channel
’s CT ratio may also be independently adjusted.
Each current input can be matched to any voltage phase. CT inputs may be reversed.
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Modem Selection
-
0
4
0
0:
not used
1:
Internal GSM modem
GPRS Connection
Enable
-
0
1
0
0:
GPRS disabled
1:
GPRS enabled
Ping Period
sec
30
900
120
The unit will check the availability of the
internet connection with this interval.
Modbus over IP Port
-
0000
65535
502
Internal Modbus TCP/IP server port.
The unit answers only queries coming
from this port number.
Site ID
The site identity string is designed to identify the current controller. This is
the site Id string sent at the beginning of SMS messages, e-mails and web
page headers for the identification of the genset sending the message. Any
20 character long string may be entered.
Serial Number
The engine serial number string is designed to identify the current
controller.This string is added to GSM-SMS messages, e-mails, web page
headers etc
… Any 20 character long string may be entered.
SMS Enable
-
0
1
0
0:
SMS messages disabled
1:
SMS messages enabled
SMS on Output Change
-
0
1
0
0:
no SMS on any output relay change
1:
SMS sent on output relay change.
SMS on IP Change
-
0
1
0
This parameter controls SMS sending
when IP address of GPRS connection is
changed. No warnings generated.
0:
no SMS on IP change
1:
SMS sent on IP change
SMS Commands
Enabled
-
0
1
0
0: SMS commands not accepted
1: SMS commands are accepted but
from listed telephone numbers only.
SMS Phone Numbers
These telephone number buffers accept up to 16 digits and are used for
SMS sending.
E-mail server port
-
0000
65535
587
Server port used in e-mail sending.
E-mail on IP Change
-
0
1
0
This parameter controls e-mail sending
when IP address of GPRS or ethernet
connection is changed. No warnings
generated.
0: no e-mail on IP change
1: e-mail sent on IP change
11.4. GSM MODEM PARAMETERS