DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 13 -
Number of inputs:
2 inputs, all configurable
Input type:
Opto-isolated digital input
Function selection:
from list
Contact type:
Normally open or normally closed (programmable)
Minimum pulse duration:
250ms
Active level:
85-305VAC
Isolation:
1000VAC, 1 minute
Noise filtering:
yes
Structure:
Relay output, normally open contact. One terminal is internally
connected to the common terminal for both relays.
Max switching current:
5A @250VAC
Max switching voltage:
250VAC
Max switching power:
1250VA
Structure:
RS-485, isolated.
Connection:
3 wires (A-B-GND). Half duplex.
Baud rate:
2400-115200 bauds, selectable
Data type:
8 bit data, no parity, 1 bit stop
Termination:
External 120 ohms required
Common mode voltage:
-0.5 VDC to +7VDC, internally clamped by transient suppressors.
Max distance:
1200m @ 9600 bauds (with 120 ohms balanced cable)
200m @ 115200 bauds (with 120 ohms balanced cable)
Isolation:
1000VAC, 1 minute
The RS-485 port features MODBUS-RTU protocol. Multiple modules (up to 128) can be paralleled on the
same RS-485 bus for data transfer to automation or building management systems.
The RS-485 port provides also a good solution for distant PC connection where RainbowPlus program will
enable programming, control and monitoring.
3.5. RELAY OUTPUTS
3.6. RS-485 PORT
3.4. DIGITAL INPUTS