DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 7 -
Before installation:
▪
Read the user manual carefully, determine the correct connection diagram.
▪
Install to the panel base or DIN rail. In order to install to panel base, pull mounting tabs at corners.
▪
Make electrical connections with plugs removed from sockets, then place plugs to their sockets.
▪
Be sure that adequate cooling is provided.
▪
Be sure that the temperature of the environment will not exceed the maximum operating temperature in any
case.
▪
Be sure that the unit is not subject to water spill.
Below conditions may damage the device:
▪
Incorrect connections.
▪
Incorrect power supply voltage.
▪
Voltage at measuring terminals beyond specified range.
▪
Voltage applied to digital inputs over specified range.
▪
Current at measuring terminals beyond specified range.
▪
Overload or short circuit at relay outputs
▪
Connecting or removing data terminals when the unit is powered-up.
▪
High voltage applied to communication ports.
▪
Ground potential differences at non-isolated communication ports.
▪
Excessive vibration, direct installation on vibrating parts.
Below conditions may cause abnormal operation:
▪
Power supply voltage below minimum acceptable level.
▪
Power supply frequency out of specified limits
▪
Phase order of voltage inputs not correct.
▪
Current transformers not matching related phases.
▪
Current transformer polarity incorrect.
▪
Missing grounding.
Current measurement is made with CTs provided together
with the module.
Do not apply direct connection, do not use 1A/5A current
transformers.
1. INSTALLATION INSTRUCTIONS