DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 45 -
The unit kepps waveforms of 30 current channels and 6 voltage channels.
The required channel number should be written to
“
COMMAND ARRAY>Oscilloscope Channel Number
” .
ADDRESS
(decimal)
R / W
DATA
SIZE
COEFF.
DESCRIPTION
21721
R
16 bit
-
Oscilloscope channel (0-5:voltages, 6-35:Currents)
21722-
21821
R
100x16bit
-
Oscilloscope point value (16 bit signed integer). Each register
gives the value of a point on thew X axis. The graphic is
represented by a total number of 100 points.
ADDRESS
(decimal)
R / W
DATA
SIZE
COEFF.
DESCRIPTION
21830
R
16 bit
-
Device type (always 0x0430)
21831
R
16 bit
-
Firmware version
ADDRESS
(decimal)
R / W
DATA
SIZE
COEFF.
DESCRIPTION
22351
R
32 bit
-
Bit_00: high voltage alarm
Bit_01: low voltage alarm
Bit_02: high frequency alarm
Bit_03: low frequency alarm
Bit_04: high THD-V alarm
Bit_05: voltage unbalance alarm
Bit_06: Phase order alarm
Bit_07: digital Input-1 alarm
Bit_08: digital Input-2 alarm
Bit_09: panel alarm
Bit_10: high temperature alarm
Bit_11..31: -
22353
R
32 bit
-
Bit_00: Input-01high active power alarm
Bit_01: Input-02 high active power alarm
Bit_02: ...
Bit_03: ...
Bit_29: Input-30 high active power alarm
Bit_30-31: -
22355
R
32 bit
-
Bit_00: Input-01low active power alarm
Bit_01: Input-02 low active power alarm
Bit_02: ...
Bit_03: ...
Bit_29: Input-30 low active power alarm
Bit_30-31: -
16.13. ALARM INFORMATION
16.12. DEVICE INFORMATION
16.11. OSCILLOGRAPHIC RECORDS