DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 30 -
THD-I Alarm
%
0
100
0
If theTHD of any current channel goes
above this limit, this will cause an alarm.
If this limit is 0 then the alarm is not
controlled.
THD-I Alarm Duration
sec
0
255
1
If the THD of any current channel goes
outside of the limits during this timer, a
THD-I alarm will occur.
THD-I Alarm Lock
Enable
-
0
1
1
0: alarm non latching
1: latching alarm
Voltage Unbalance Alarm
%
0
100
0
If the Voltage Unbalance goes above
this limit, this will cause an alarm.
If this limit is 0 then the alarm is not
controlled.
Voltage Unbalance Alarm
Duration
sec
0
255
1
If the Voltage Unbalance goes outside
of the limits during this timer, a THD-I
alarm will occur.
Voltage Unbalance Alarm
Lock Enable
-
0
1
1
0: alarm non latching
1: latching alarm
Demand Interval
min
0
1000
15
This is the period used in demand
calculations.
Counter Unit
-
0
1
1
0: kWh
1: MWh
11.2. ELECTRICAL PARAMETERS GROUP (continued)