NUFLO™
Scanner
®
2000 microEFM
Quick
Start
Part No. 30165024, Rev. A
Installing the Scanner 2000
Direct Mount
To install the Scanner 2000 microEFM using a direct mount to
an orifice or cone meter run, perform the following steps:
1. Determine the best location for the Scanner 2000.
a. For horizontal meter runs, locate process connections at
the top of the line, and mount the Scanner 2000 above
the pressure connections at the pipe.
b. For vertical meter runs, make sure pipeline flow is up-
ward.
2. Locate the H and L markings on the Scanner 2000 transmit-
ter designating high-pressure and low-pressure ports, and
connect a valve manifold (if desired) to the transmitter.
3. Connect the orifice flanges to the Scanner 2000/manifold
assembly, matching the upstream tap to the high-pressure
manifold port and the downstream tap to the low-pressure
manifold port.
ADJUSTABLE HEAD DESIGN.
When the sensor is oriented ap-
propriately for pressure connec-
tions, the position of the Scanner
display may need to be adjusted.
To change the orientation of the
head, loosen the set screw in the
MVT adapter, rotate the head
no more than 180 degrees and
tighten the set screw.
Remote Mount
To install the Scanner 2000 microEFM remotely from the
flow run, perform the following steps:
1. Mount the Scanner to a flat, vertical surface, or bolt
to a 2-in. pipe using optional pole-mount hardware.
2. Install process tubing between the orifice run and
the manifold, making sure that the upstream pres-
sure tap is connected to the high-pressure manifold
port and the downstream pressure tap is connected
to the low-pressure manifold port. Slope all piping
at least 1-inch per linear foot to avoid trapping
liquid.
3. Use a suitable compound or tape on all threaded
process connections.
4. Position all shutoff and bypass valves so they are
accessible from the front of the instrument.
5. Check the manifold for leaks.
POLE-MOUNT OPTION.
An optional pole mount kit
(Part No. 9A-30028004)
allows the Scanner 2000 to
be mounted to a 2-in.
vertical or horizontal pipe.
The kit includes a mounting
bracket, two U-bolts and
screws for connecting the
bracket to the Scanner 2000
enclosure.