Wiring the Scanner 2000

CAUTION—All field wiring must conform to the National 

Electrical Code, NFPA 70, Article 501-4(b) for installations within 

the United States or the Canadian Electric Code for installa-

tions within Canada.  Local wiring ordinances may also apply.  

All field wiring must have a wire range of 22 to 14 AWG and 

terminal block screws must be tightened to a minimum torque 

of 5 to 7 in-lbs. to secure the wiring within the terminal block.  

Only personnel who are experienced with field wiring should 

perform these procedures.

 

 

WARNING—To prevent ignition of hazardous atmospheres, do 

not remove the cover while circuits are alive. Under normal 

conditions, the Scanner 2000 microEFM poses no hazard when 

opened in a safe area.

SWITCH

J1

TB1

BATTERY

13

14

J2

SCANNER 2000

Main Circuit Board

PN: 30160010

TF

M 1

R

TD

I

+

R

+

R

-

I

-

+

2
3
4
5
6

1

P

O

W

E

R

P

O

R

T 2

P

O

R

T 1

+

+

+

7
8
9

10
11
12

TB2

TB3

DIG OUT 1

TB2

PO

W

ER

PO

R

T 2

PO

RT

 1

6 TO 30 VDC

POWER SUPPLY

+

+

+

7
8
9

10
11
12

EXTERNAL POWER INPUT

TB1

TF

M1

R

T

D

I

+

+

R

+

R

-

I

-

2
3
4
5
6

1

+

RTD

RTD

-

WHITE

RED

WHITE

RED

I-

I

+

RTD INPUT

TURBINE INPUT

R

TD

TURBINE

MAGNETIC 

PICKUP

B

A

TB1

TF

M1

I

+

+

R

+

R

-

I

-

2
3
4
5
6

1

BLACK

RED

DIGITAL  OUTPUT

13

14

Leave this 

end of shield 

disconnected.

POWER SUPPLY

5 to 30 VDC

Resistor may be included in pulse readout 

device. Size the resistor to limit the current 

to 60 mA.

PULSE READOUT

DEVICE

 

 

TB3

Field wiring enters the Scanner 2000 microEFM through either of two 

¾-in. NPT conduit openings in the enclosure and connects to three 

terminal blocks on the main circuit assembly (TB1, TB2 and TB3). For 

instructions on wiring an optional expansion circuit board, see the 

Scanner 2000 Hardware Manual.

RS-485 TO RS-232 CONVERTER

TX+

TX

-

TB2

PO

W

ER

PO

R

T

 

2

PO

RT

 

1

+

+

+

7
8
9

10
11
12

TD(B)

TD(A)

GND

Part No. 9A-101283116

PORT 1 OR PORT 2 CAN BE 

CONNECTED TO THE 232/485 

CONVERTER

RS-232 9-PIN  CONNECT

OR

232/485

CONVERTER

Scanner/Laptop Connection Options

Scanner 2000 microEFMs connect to a laptop three ways:

• 

using an optional USB adapter and user-supplied USB cable 

(external port for easy access)

• 

using an RS-485 to RS-232 converter cable (wires to circuit board)

• 

using an optional COM adapter and RS-485 to RS-232 converter 

cable (external port for easy access)

TX+

TX

-

TB2

PO

W

ER

PO

R

T

 

2

PO

RT

 

1

+

+

+

7
8
9

10
11
12

TD(B)

TD(A)

GND

Part No. 101283116

PORT 1 OR PORT 2 CAN BE 

CONNECTED TO THE 232/485 

CONVERTER

RS-232 9-PIN  CONNECT

OR

232/485

CONVERTER

USB ADAPTER (OPTIONAL)  

Содержание NUFLO Scanner 2000 microEFM

Страница 1: ...ay need to be adjusted To change the orientation of the head loosen the set screw in the MVT adapter rotate the head no more than 180 degrees and tighten the set screw Remote Mount To install the Scan...

Страница 2: ...UP B A TB1 TFM1 I R R I 2 3 4 5 6 1 BLACK RED DIGITAL OUTPUT 13 14 Leave this end of shield disconnected POWER SUPPLY 5 to 30 VDC Resistor may be included in pulse readout device Size the resistor to...

Страница 3: ...digit to the left Repeat using UP ARROW LOG and LEFT ARROW DISPLAY to enter all remaining digits Press ENTER SAVE Keypad Configuration Controls Remove the instrument cover to access the keypad Each of...

Страница 4: ...is the control center for the Scanner 2000 and provides quick and easy access to the most commonly performed tasks From this screen the user can view real time totals and flow rates input data and sy...

Страница 5: ...o perform Then select the parameter you want to calibrate 2 Click Acquire Point to enter a new calibration point and enter the applied calibration value at the prompt Or click Load Calibration From to...

Страница 6: ...od used Click Change Task to select a new maintenance task 1 Select the task you want to perform 3 Click Save Changes to save the new parameters to memory 2 Enter new parameters in the fields provided...

Страница 7: ...to specify plate parameters 9 Enter base conditions specific to the location 10 Click Change Composition to specify the gas composition Percentages must total 100 8 Specify pipe parameters 11 Click O...

Страница 8: ...screen Download Screens Part No 9A 30165024 Rev 03 To download data simply press the Download button and select the range and type of files to be downloaded Daily and interval logs can be viewed or p...

Отзывы: