126
A p p e n d i x J
5
DI
13089
NORMAL
FAULT
FAULT Allows telemetry
to sense float
sequence faults
and activate the
alarm
6
DI
13090
NORMAL
FAULT
FAULT Detects transducer
malfunctions and
activates the alarm
7
DI
13091
NORMAL
FAULT
FAULT Detects the
presence of
AC Power and
activates the alarm
when absent
8
Configuration DI
13092
-
UPDATED
Detects if the local
configuration has
been updated;
activates the alarm
for update
* For analog points, the Low State Label column gives the point’s Low engineering value followed by its Low raw value.
** For analog points, the High State Label column gives the point’s High engineering value followed by its High raw value.
Module D - DCM001
Point # Point Name
Point
Type
Modbus
Register
Low State
Label
High State
Label
Alarm
State
Description
1
Pump 1
Disable
DO
1025
OFF
ON
Allows telemetry to turn off
Pump 1 regardless of pump’s
TCU state
2
Pump 2
Disable
DO
1026
OFF
ON
Allows telemetry to turn off
Pump 2 regardless of pump’s
TCU state
3
Pump 3
Disable
DO
1027
OFF
ON
Allows telemetry to turn off
Pump 3 regardless of pump’s
TCU state
4
Pump 1
Override
DO
1028
OFF
ON
Allows telemetry to turn on
Pump 1 regardless of pump’s
TCU state
5
Pump 2
Override
DO
1029
OFF
ON
Allows telemetry to turn on
Pump 2 regardless of pump’s
TCU state
6
Pump 3
Override
DO
1030
OFF
ON
Allows telemetry to turn on
Pump 3 regardless of pump’s
TCU state
7
Pump 1 Starter DI
13319
NORMAL
FAULT
FAULT Allows telemetry to sense a
Pump 1 starter failure and
activate the alarm
Содержание TCU800
Страница 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Страница 2: ...Intentionally left blank ...
Страница 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Страница 8: ...ii Intentionally left blank ...
Страница 10: ...ii Intentionally left blank ...
Страница 49: ...39 S e t u p Externally Powered Non submersible Transducer TCU Powered Non submersible Transducer ...
Страница 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Страница 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Страница 58: ...48 C h a p t e r 5 Advanced Settings About ...
Страница 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Страница 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Страница 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Страница 157: ...147 D a t a F l o w S y s t e m s I n c ...
Страница 158: ...148 D a t a F l o w S y s t e m s I n c ...
Страница 159: ...149 D a t a F l o w S y s t e m s I n c ...
Страница 160: ......
Страница 161: ...151 D a t a F l o w S y s t e m s I n c ...
Страница 162: ...Data Flow Systems Inc 605 N John Rodes Blvd Melbourne Florida 32934 321 259 5009 www dataflowsys com ...