6
C h a p t e r 2
Top Connector 2: P3
PIN# Name
Description
Electrical Rating
Module
Address
P3-1 C_CT+
C-phase current transformer positive connection
<24V / Not Rated
P3-2 C_CT-
C-phase current transformer negative connection
<24V / Not Rated
P3-3 B_CT+
B-phase current transformer positive connection
<24V / Not Rated
P3-4 B_CT-
B-phase current transformer negative connection
<24V / Not Rated
P3-5 A_CT+
A-phase current transformer positive connection (wye
setup only)
<24V / Not Rated
P3-6 A_CT-
A-phase current transformer negative connection
(wye setup only)
<24V / Not Rated
P3-7
0-5VDC or 0-10VDC or 4-20mA signal from trans-
ducer; return signal at P3-8; jump P3-9 to P3-8 to use
as a 4-20mA input
<24V / Not Rated
I1*
P3-8 ANALOG3-
- return signal for (P3-7)
<24V / Not Rated
P3-9 SHUNT
250Ω shunt resistor; jump to P3-8 to use a 4-20mA
signal for (P3-7)
<24V / Not Rated
P3-10
0-5VDC or 0-10VDC or 4-20mA signal from trans-
ducer; return signal at P3-11; jump P3-12 to P3-11 to
use as a 4-20mA input
<24V / Not Rated
I2*
P3-11 ANALOG4-
- return signal for (P3-10)
<24V / Not Rated
P1-10 BEMGND
Isolated ground (wire to BEM001, pin 12)
<24V / Not Rated
--
P1-11 BEM_PWR
Isolated power (wire to BEM001, pin 10)
<24V / Not Rated
--
P1-12 BEM_CTS
Isolated clear to send (wire BEM001, pin 6)
<24V / Not Rated
--
P1-13 BEM_RXD
Isolated receive data (wire to BEM001, pin 4)
<24V / Not Rated
--
P1-14 BEM_TXD
Isolated transmit data (wire to BEM001, pin 2)
<24V / Not Rated
--
P1-15 BEM_RTS
Isolated request to send (wire to BEM001, pin 8)
<24V / Not Rated
--
P1-16 ALM_HORN Load side of alarm horn relay (NO)
120VAC, 60HZ, 1A,
0-24VDC, 1A
B5
P1-17 ALM_LITE
Load side of alarm light relay (NC)
120VAC, 60HZ, 1A,
0-24VDC, 1A
B6
P1-18 ALM_PWR
Line side of alarm relays
120VAC, 60HZ, 2A,
0-24VDC, 2A
--
P1-19 AUX_OUT
Load side of auxiliary relay
120-240VAC, 60HZ, 1A,
Pilot Duty
B4
P1-20 AUX_PWR
Load side of auxiliary relay
120-240 VAC, 60HZ, 1A --
P1-21 MTR3_STR
Load side of motor starter 3 relay
120-240 VAC, 60HZ, 1A,
Pilot Duty
B3
P1-22 MTR2_STR
Load side of motor starter 2 relay
120-240 VAC, 60HZ, 1A,
Pilot Duty
B2
P1-23 MTR1_STR
Load side of motor starter 1 relay
120-240 VAC, 60HZ, 1A,
Pilot Duty
B1
P1-24 STRT_PWR
Line side of motor start relays
120-240 VAC, 60HZ, 3A
--
Содержание TCU800
Страница 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Страница 2: ...Intentionally left blank ...
Страница 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Страница 8: ...ii Intentionally left blank ...
Страница 10: ...ii Intentionally left blank ...
Страница 49: ...39 S e t u p Externally Powered Non submersible Transducer TCU Powered Non submersible Transducer ...
Страница 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Страница 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Страница 58: ...48 C h a p t e r 5 Advanced Settings About ...
Страница 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Страница 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Страница 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Страница 157: ...147 D a t a F l o w S y s t e m s I n c ...
Страница 158: ...148 D a t a F l o w S y s t e m s I n c ...
Страница 159: ...149 D a t a F l o w S y s t e m s I n c ...
Страница 160: ......
Страница 161: ...151 D a t a F l o w S y s t e m s I n c ...
Страница 162: ...Data Flow Systems Inc 605 N John Rodes Blvd Melbourne Florida 32934 321 259 5009 www dataflowsys com ...