U n i t O v e r v i e w
Lead Off Level
Lead Off is the maximum operational level of a tank. Lead pump is stopped
when the well’s level is
above
the Lead Off level.
Lag Off Level (duplex and triplex
stations only)
Lag (second) pump is stopped. Lag Off is active when the tank’s level is
above
Lag Off level.
Lag2 Off Level (triplex stations only)
Lag2 (third) pump is stopped. Lag2 Off is active when the tank’s level is
below
Lag2 Off level.
Lead Level
Lead (first) pump is started. Lead is active when the tank’s level is
below
the
Lead level.
Lag Level (duplex and triplex stations
only)
Lag (second) pump is started. Lag is active when the tank’s level is
below
the
Lag level.
Lag2 Level (triplex stations only)
Lag2 (third) pump is started. Lag2 is active when the tank’s level is
below
the
Lag2 level.
Low Level
All pumps are stagger started and alarms are activated. Low is active when the
tank’s level is
below
Low level. Must be set below all other levels.
Pump Alternation
The TCU includes a pump alternator function that can be used to minimize pump cycle times or equalize pump run times.
When enabled, the alternator updates each time it starts a pump. If a pump fails to start, the alternator advances to the next
available pump. Pumps can be taken out of service with the H-O-A switches and the TCU will continue to alternate the
remaining pumps.
The following alternation options are available:
• Alternate among all available pumps.
• Alternate between pumps 1 and 2 (High Service Pump option).
• Alternate between pumps 2 and 3 (Jockey Pump option).
• Disable pump alternation
Содержание TCU800
Страница 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Страница 2: ...Intentionally left blank ...
Страница 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Страница 8: ...ii Intentionally left blank ...
Страница 10: ...ii Intentionally left blank ...
Страница 49: ...39 S e t u p Externally Powered Non submersible Transducer TCU Powered Non submersible Transducer ...
Страница 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Страница 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Страница 58: ...48 C h a p t e r 5 Advanced Settings About ...
Страница 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Страница 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Страница 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Страница 157: ...147 D a t a F l o w S y s t e m s I n c ...
Страница 158: ...148 D a t a F l o w S y s t e m s I n c ...
Страница 159: ...149 D a t a F l o w S y s t e m s I n c ...
Страница 160: ......
Страница 161: ...151 D a t a F l o w S y s t e m s I n c ...
Страница 162: ...Data Flow Systems Inc 605 N John Rodes Blvd Melbourne Florida 32934 321 259 5009 www dataflowsys com ...