T C U T r a n s d u c e r C o n f i g u r a t i o n E x a m p l e s
TCU Settings (Transducer with Floats Backup)
Name
Setting
Description
For more information, see...
Transducer type
4-20 mA or 0-5 Volts Select 4-20 mA or 0-5 Volts for
systems using analog transducers.
page 52
Low Float
Enabled or Disabled Enable this setting to use a low level
float to override normal pump control
if a transducer fault occurs.
page 54
High Float
Enabled
Enable this setting to use a high level
float to override normal pump control
if a transducer fault occurs.
page 54
Fault Mode
Floats
Select Floats to have the TCU switch
to float control when a transducer fault
occurs.
page 54
Transducer High Float
Fault
Enabled
Enable to generate a transducer fault
when a high float condition occurs.
page 54
Transducer Low Level
Fault
Enabled
Enable to generate a transducer fault
when a low float condition occurs.
page 54
Bubbler Noise Fault
Enabled or Disabled Enable only if the system is a bubbler
system and you want to generate a
transducer fault when the TCU doesn’t
detect air-pump induced noise.
page 54
High Float Override
Enabled or Disabled Enable this setting to give the High
float precedence in the event of an Off
float failure when the TCU is in Floats
fault mode.
page 54
Minimum Run
1.0
Minimum time pumps should run.
Used to prevent short cycling.
page 52
Minimum Off
0.5
Minimum time pumps should remain
off. Used to prevent short cycling.
page 52
Response to Fault Conditions (Transducer with Floats Backup)
Fault(s)
Alarms
Pump Operation
Behavior
Transducer low
condition
• Transducer fault
alarm
• Low well alarm
All pumps off
Control switches to float inputs. Low well and
transducer fault alarms are generated. If float
inputs agree, all pumps are turned off. The low
well alarm clears if the transducer returns to
normal range. However, the transducer fault
alarm remains active and control remains with
floats until the TCU has been reset.
Concurrent off
float and lead float
conditions
Transducer fault
Normal pump
operation
Example of normal operation under floats
control, regardless of which event triggered the
transducer fault.
Содержание TCU800
Страница 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Страница 2: ...Intentionally left blank ...
Страница 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Страница 8: ...ii Intentionally left blank ...
Страница 10: ...ii Intentionally left blank ...
Страница 49: ...39 S e t u p Externally Powered Non submersible Transducer TCU Powered Non submersible Transducer ...
Страница 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Страница 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Страница 58: ...48 C h a p t e r 5 Advanced Settings About ...
Страница 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Страница 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Страница 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Страница 157: ...147 D a t a F l o w S y s t e m s I n c ...
Страница 158: ...148 D a t a F l o w S y s t e m s I n c ...
Страница 159: ...149 D a t a F l o w S y s t e m s I n c ...
Страница 160: ......
Страница 161: ...151 D a t a F l o w S y s t e m s I n c ...
Страница 162: ...Data Flow Systems Inc 605 N John Rodes Blvd Melbourne Florida 32934 321 259 5009 www dataflowsys com ...