Options under the Analog menu are used to configure the
pump settings to adhere to the physical measurements of a
particular well.
High Level
• Pump Up mode – In tank filling operations, the TCU stops all three pumps
and activates alarms when the tank’s level rises above this set point. This level
must be set above all other levels.
• Pump Down mode – In well emptying operations, the TCU starts all three
pumps and activates alarms when the well’s level rises above this set point.
This level must be set above all other levels.
Lag 2 On Level
Note: This setting is used for triplex (three-pump) stations only.
• Pump Up mode – In tank filling operations, the TCU starts the Lag2, or third,
pump when the tank’s level falls below this set point.
• Pump Down mode – In well emptying operations, the TCU starts the Lag2, or
third, pump when the well’s level rises above this set point.
Lag 2 Off Level
Note: This setting is used for triplex (three-pump) stations only.
• Pump Up mode – In tank filling operations, the TCU turns off the Lag2, or
third, pump when the tank’s level rises above this set point.
• Pump Down mode – For well emptying operations, the TCU turns off the
Lag2, or third, pump when the well’s level falls below this set point.
• This can be set to the same value as LeadOff Pt for either operation.
Lag 1 On Level
Note: This setting is used for duplex (two-pump) and triplex (three-pump) stations
only.
• Pump Up mode – In tank filling operations, the TCU starts the Lag, or second,
pump when the tank’s level falls below this set point.
• Pump Down mode – In well emptying operations, the TCU starts the Lag, or
second, pump when the well’s level rises above this set point.
Lag 1 Off Level
Note: This setting is used for duplex (two-pump) and triplex (three-pump) stations
only.
• Pump Up mode – In tank filling operations, the TCU turns off the Lag, or
second, pump when the tank’s level rises above this set point.
• Pump Down mode – In well emptying operations, the TCU turns off the Lag,
or second, pump when the well’s level falls below this set point.
• This can be set to the same value as LeadOff Pt for either operation.
Analog
Содержание TCU800
Страница 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Страница 2: ...Intentionally left blank ...
Страница 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Страница 8: ...ii Intentionally left blank ...
Страница 10: ...ii Intentionally left blank ...
Страница 49: ...39 S e t u p Externally Powered Non submersible Transducer TCU Powered Non submersible Transducer ...
Страница 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Страница 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Страница 58: ...48 C h a p t e r 5 Advanced Settings About ...
Страница 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Страница 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Страница 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Страница 157: ...147 D a t a F l o w S y s t e m s I n c ...
Страница 158: ...148 D a t a F l o w S y s t e m s I n c ...
Страница 159: ...149 D a t a F l o w S y s t e m s I n c ...
Страница 160: ......
Страница 161: ...151 D a t a F l o w S y s t e m s I n c ...
Страница 162: ...Data Flow Systems Inc 605 N John Rodes Blvd Melbourne Florida 32934 321 259 5009 www dataflowsys com ...