O p e r a t i n g P r o c e d u r e s
Auto-Configuring
At this time, using a TCU001 PLC configuration will cause an error in the TCU800. To avoid this, first transfer the existing
configuration of the TCU800 using HyperTAC PLC editor. Then save the .plc file, create an auto-config file, and upload it
to the appropriate station you want to auto-config.
Remote Configuration Changes
Changing configuration values using the PLC editor is supported but requires that the settings be transferred initially from
the TCU800 to the remote PLC editor (once). If taking this step, disregard the configuration values listed in the Autodialer
section of the editor as the TCU800 does not support Autodialer and the settings have been repurposed for other use. This
workaround is temporary. If only changing a few configuration values, this step can be bypassed as only the changed values
need to be selected and sent.
For more detail on remote configuration changes see the HT4 User Guide, available on dataflowsys.com.
Advanced Settings
Radio Test Mode
Selecting the Radio Test Mode option displays a
prompt confirming the activation of the radio test
mode. If ‘Yes’ is selected, the antenna needs to be
manually aimed to record signal loss and adjusted
appropriately to get it within an acceptable margin. If
‘No’ is selected, the pop up will clear and the screen
will return to the Advanced Settings menu.
Содержание TCU800
Страница 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Страница 2: ...Intentionally left blank ...
Страница 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Страница 8: ...ii Intentionally left blank ...
Страница 10: ...ii Intentionally left blank ...
Страница 49: ...39 S e t u p Externally Powered Non submersible Transducer TCU Powered Non submersible Transducer ...
Страница 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Страница 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Страница 58: ...48 C h a p t e r 5 Advanced Settings About ...
Страница 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Страница 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Страница 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Страница 157: ...147 D a t a F l o w S y s t e m s I n c ...
Страница 158: ...148 D a t a F l o w S y s t e m s I n c ...
Страница 159: ...149 D a t a F l o w S y s t e m s I n c ...
Страница 160: ......
Страница 161: ...151 D a t a F l o w S y s t e m s I n c ...
Страница 162: ...Data Flow Systems Inc 605 N John Rodes Blvd Melbourne Florida 32934 321 259 5009 www dataflowsys com ...