53
O p e r a t i n g P r o c e d u r e s
High Float (Disabled/Enabled)
If a high level float is being used, High Float must be enabled. If a high level float
is not connected and High Float is enabled, there is no effect on the operation of the
TCU. In a Pump Down Mode (Lift Station) system, all pumps are stagger-started
on a high float condition. In a Pump Up Mode (Storage Tank) system, all pumps are
stopped on a high float condition. A high float condition generates a high well alarm
and an optional transducer fault alarm.
Low Float (Disabled/Enabled)
If a low level float is being used, Low Float must be enabled. Low Float must be
disabled if a low level float is not connected. (If Low Float is not disabled, the
Low Well alarm will interfere with station operation.) In a Pump Down Mode (Lift
Station) system, all pumps are stopped on a low float condition. In a Pump Up
Mode (Storage Tank) system, all pumps are stagger-started on a low float condition.
A low float condition generates a low well alarm and an optional transducer fault
alarm.
XDCR High Float Fault
(Disabled/Enabled)
When this option is enabled, a high float condition generates a transducer fault and
switches control to the configured fault mode. Leaving the option disabled leaves
pump control on the primary transducer whenever a high float condition occurs or
the transducer reaches or exceeds 20 mA.
XDCR Low Level Fault
(enabled/disabled)
When this option is enabled, a low float condition OR a transducer low level
condition (level drops below Low set point) generates a transducer fault and
switches control to the configured fault mode. Leaving the option disabled leaves
pump control on the primary transducer whenever a low float or transducer low
level condition occurs.
High Float Override (Disabled/
Enabled)
When this option is enabled, the High Float is given precedence in the event of an
Off float failure when the TCU is in Float control mode (this can be a floats-only
system or an analog transducer system that uses floats for backup).
Options under the Radio Menu are used to configure the
TCU800’s station address and radio protocol settings.
Radio
Содержание TCU800
Страница 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Страница 2: ...Intentionally left blank ...
Страница 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Страница 8: ...ii Intentionally left blank ...
Страница 10: ...ii Intentionally left blank ...
Страница 49: ...39 S e t u p Externally Powered Non submersible Transducer TCU Powered Non submersible Transducer ...
Страница 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Страница 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Страница 58: ...48 C h a p t e r 5 Advanced Settings About ...
Страница 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Страница 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Страница 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Страница 157: ...147 D a t a F l o w S y s t e m s I n c ...
Страница 158: ...148 D a t a F l o w S y s t e m s I n c ...
Страница 159: ...149 D a t a F l o w S y s t e m s I n c ...
Страница 160: ......
Страница 161: ...151 D a t a F l o w S y s t e m s I n c ...
Страница 162: ...Data Flow Systems Inc 605 N John Rodes Blvd Melbourne Florida 32934 321 259 5009 www dataflowsys com ...