C h a p t e r 4
Motor Starter Circuit Wiring
Simplex stations use only MTR1_STR. Duplex stations use MTR1_STR and MTR2_STR. Triplex stations use all of the
motor starter outputs. Unused starter outputs can be used as auxiliary outputs with control provided by telemetry.
Alarm Light and Horn Outputs
The alarm outputs use mechanical relays to drive up to 0.5 A at 120 VAC or 1 A at 0-24 VDC. The addition of 1 A slow
blow fuses on the TCU outputs is recommended to protect the TCU’s alarm relays from short circuits. The alarm light
output is a set of contacts that are closed when the TCU is powered down.
The alarm light output is designed to energize an incandescent lamp. Any other application requires an
interposing relay, especially strobe lights due to their high peak current demands.
Alarm Horn and Alarm Light Wiring
Содержание TCU800
Страница 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Страница 2: ...Intentionally left blank ...
Страница 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Страница 8: ...ii Intentionally left blank ...
Страница 10: ...ii Intentionally left blank ...
Страница 49: ...39 S e t u p Externally Powered Non submersible Transducer TCU Powered Non submersible Transducer ...
Страница 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Страница 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Страница 58: ...48 C h a p t e r 5 Advanced Settings About ...
Страница 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Страница 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Страница 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Страница 157: ...147 D a t a F l o w S y s t e m s I n c ...
Страница 158: ...148 D a t a F l o w S y s t e m s I n c ...
Страница 159: ...149 D a t a F l o w S y s t e m s I n c ...
Страница 160: ......
Страница 161: ...151 D a t a F l o w S y s t e m s I n c ...
Страница 162: ...Data Flow Systems Inc 605 N John Rodes Blvd Melbourne Florida 32934 321 259 5009 www dataflowsys com ...