55
O p e r a t i n g P r o c e d u r e s
Options under the Auxiliary Menu are used to configure the
auxiliary input, auxiliary output, and time delay relay.
Auxiliary
Aux Output Turns (off/on)
Together, the settings AuxOut Turns (On/Off) and AuxIn Turns (On/Off) define
how AUX_OUT responds when the state of AUX_IN changes. (e.g. AUX_OUT
turns OFF when AUX_IN turns OFF or AUX_OUT turns OFF when AUX_IN turns
ON.)
Delay After
This setting determines the amount of time that is allowed to pass before turning
the auxiliary output on or off. Seconds after can be set between 0 and 510 seconds
in one-second increments. Assigning this setting a value of zero disconnects the
AUX_IN and the AUX_OUT and makes them available to telemetry as general
monitor and control points.
Aux Input Turns (off/on)
Together, the settings AuxOut Turns (On/Off) and AuxIn Turns (On/Off) define
how AUX_OUT responds when the state of AUX_IN changes. (e.g. AUX_OUT
turns OFF when AUX_IN turns OFF or AUX_OUT turns OFF when AUX_IN turns
ON.)
Aux Input Alarm (off/on)
The TCU monitors the AUX_IN terminal (p2-12), and it can be configured to
activate the AuxIn alarm when the terminal is open or closed. If the auxiliary input
alarm has been enabled and AUX_IN enters its configured alarm state (open or
closed), an auxiliary input alarm is generated.
Aux Alarm On
If the Aux Input Alarm is enabled, the input’s alarm state must be defined (enabled/
disabled).When the terminal is in this state, an auxiliary input alarm is generated.
Pulse Counting
When enabled, this option changes the AUX input pin into a pulse counting pin.
Содержание TCU800
Страница 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Страница 2: ...Intentionally left blank ...
Страница 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Страница 8: ...ii Intentionally left blank ...
Страница 10: ...ii Intentionally left blank ...
Страница 49: ...39 S e t u p Externally Powered Non submersible Transducer TCU Powered Non submersible Transducer ...
Страница 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Страница 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Страница 58: ...48 C h a p t e r 5 Advanced Settings About ...
Страница 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Страница 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Страница 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Страница 157: ...147 D a t a F l o w S y s t e m s I n c ...
Страница 158: ...148 D a t a F l o w S y s t e m s I n c ...
Страница 159: ...149 D a t a F l o w S y s t e m s I n c ...
Страница 160: ......
Страница 161: ...151 D a t a F l o w S y s t e m s I n c ...
Страница 162: ...Data Flow Systems Inc 605 N John Rodes Blvd Melbourne Florida 32934 321 259 5009 www dataflowsys com ...