4-20 mA or 0-5 VDC Transducer with High Float (Pump Down Mode)
This is the most common configuration, combining a 4-20 ma or 0-5 VDC transducers with a high level float in the well to
prevent overflow and generate a high well alarm. Fault mode is disabled in this configuration. An optional low level float
to prevent pumping the well dry can also be applied.
High float events generate a transducer fault and high well alarm and stagger on all configured pumps. The pumps will
remain on as long as the high float condition exists. To prevent short cycling on high float transitions, the pumps adhere
to the configured minimum run and minimum off timers. In the example below the pumps will run a minimum of one
minute and remain off a minimum of 30 seconds regardless of the frequency of float transitions. Minimum run and off
timers apply to all pump operations – not just fault conditions – so these timers should be set considering the pump and
well characteristics during normal pump cycles. Conversely, low float events shut off all pumps.
Note:
If a high and low float condition exist simultaneously the low float condition takes precedence and no pumps will be
started. If the transducer is a bubbler system, an optional Noise Fault configuration can be enabled to sense a bubbler pump
failure and generate a transducer fault alarm.
RS-485 Pins
Name
Setting
Description
For more information, see...
Transducer Type
4-20 mA or 0-5 V
Select 4-20 mA or 0-5 V for
systems using analog transducers.
page 52
Low Float
Enabled or Disabled Enable this setting to use a
lowlevel float to override normal
pump control if a transducer fault
occurs.
page 54
High Float
Enabled
Enable this setting to use a
highlevel float to override normal
pump control if a transducer fault
occurs.
page 54
Fault Mode
Disabled
Disable this setting if the system
isn’t using a backup method
(other than low- and/or high-
float) for pump control when a
transducer fault occurs.
page 52
Transducer High Float Fault Enabled
Enable to generate a transducer
fault when a high float condition
occurs.
page 52
Содержание TCU800
Страница 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Страница 2: ...Intentionally left blank ...
Страница 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Страница 8: ...ii Intentionally left blank ...
Страница 10: ...ii Intentionally left blank ...
Страница 49: ...39 S e t u p Externally Powered Non submersible Transducer TCU Powered Non submersible Transducer ...
Страница 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Страница 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Страница 58: ...48 C h a p t e r 5 Advanced Settings About ...
Страница 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Страница 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Страница 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Страница 157: ...147 D a t a F l o w S y s t e m s I n c ...
Страница 158: ...148 D a t a F l o w S y s t e m s I n c ...
Страница 159: ...149 D a t a F l o w S y s t e m s I n c ...
Страница 160: ......
Страница 161: ...151 D a t a F l o w S y s t e m s I n c ...
Страница 162: ...Data Flow Systems Inc 605 N John Rodes Blvd Melbourne Florida 32934 321 259 5009 www dataflowsys com ...