125
P o l l i n g t h e T C U
2
Starter 2 Out* DI
12802
OFF
ON
Detects the state of pump
starter 2
3
Starter 3 Out* DI
12803
OFF
ON
Detects the state of pump
starter 3
4
Auxiliary Out DI
12804
OFF
ON
Detects the state of the
auxiliary output
5
Alarm Light
Status
DI
12805
OFF
ON
Detects the state of the alarm
light
6
Alarm Horn
Status
DI
12806
OFF
ON
Detects the state of the alarm
horn
7
Alarm Silence
Input
DI
12807
OFF
ON
Indicates the status of the
external alarm silence switch
8
Station
Disable
DO
520
OFF
ON
In the ON state, allows
telemetry to remove power
from all pump motors
9
AC Power
DI
12809
NORMAL
FAULT
Allows telemetry to sense AC
power failure and activate the
alarm.
10
DC Bias
DI
12810
NORMAL
FAULT
Allows telemetry to sense DC
bias failure and activate the
alarm.
* These points need not be configured when the TCU is running the pump control process, because they are being controlled by the TCU’s pump control
program. Points A1 (Pump 1), A2 (Pump 2), and A3 (Pump 3) are used to report pump status.
Module C - AMM002
Point # Point Name
Point
Type
Modbus
Register
Low State
Label*
High State
Label**
Resolution/
Units
Alarm
State
Description
1
Analog Input
1
AI
33713
4/820
20/4095
0.01/mA
Settings for the
primary analog
input
2
Analog Input
2
AI
33714
4/820
20/4095
0.01/mA
Settings for the
auxiliary analog
input
3
AI
33715
0/350
300/3102
1/VAC
Settings for Phase
AB voltage (240
option)
AI
33715
0/350
600/3114
1/VAC
Settings for Phase
AB voltage (480
option)
4
AI
33716
0/350
300/3077
1/VAC
Settings for phase
AC voltage (240
option)
AI
33716
0/350
600/3077
Settings for phase
AC voltage (480
option)
Содержание TCU800
Страница 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Страница 2: ...Intentionally left blank ...
Страница 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Страница 8: ...ii Intentionally left blank ...
Страница 10: ...ii Intentionally left blank ...
Страница 49: ...39 S e t u p Externally Powered Non submersible Transducer TCU Powered Non submersible Transducer ...
Страница 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Страница 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Страница 58: ...48 C h a p t e r 5 Advanced Settings About ...
Страница 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Страница 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Страница 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Страница 157: ...147 D a t a F l o w S y s t e m s I n c ...
Страница 158: ...148 D a t a F l o w S y s t e m s I n c ...
Страница 159: ...149 D a t a F l o w S y s t e m s I n c ...
Страница 160: ......
Страница 161: ...151 D a t a F l o w S y s t e m s I n c ...
Страница 162: ...Data Flow Systems Inc 605 N John Rodes Blvd Melbourne Florida 32934 321 259 5009 www dataflowsys com ...