4.1.3 Extended Status Words
Bit
Hex
Dec
0
1
1
Ramping
Off
1
2
2
AMA running
Hand/Auto
2
4
4
Start CW/CCW
0
3
8
8
0
0
4
10
16
0
0
5
20
32
0
Relay 12 active
6
40
64
0
0
7
80
128
Output
current high
Control Ready
8
100
256
Output
current low
Drive Ready
9
200
512
0
Quick Stop
10
400
1024
0
DC Brake
11
800
2048
0
Stop
12
1000
4096
0
0
13
2000
8192
Braking
Freeze Output
Request
14
4000
16384
0
Freeze Output
15
8000
32768
OVC active
Jog Request
16
10000
65536
AC brake
Jog
17
20000
131072
0
Start request
18
40000
262144
0
Start
19
80000
524288
0
0
20
100000
1048576
0
Start Delay
21
200000
2097152
Local Ref./
Remote Ref.
Sleep
22
400000
4194304
0
Sleep boost
23
800000
8388608
0
Running
24
1000000
16777216
0
Bypass
25
2000000
33554432
0
Fire Mode
26
4000000
67108864
0
External Interlock
27
8000000
134217728
0
Firemodelimi-
texceed
28
10000000
268435456
0
FlyStart Active
29
20000000
536870912
0
0
30
40000000 1073741824
0
0
31
80000000 2147483648 Database busy
0
4.1.4 Fault Messages
WARNING/ALARM 2, Live zero error
This warning or alarm will only appear if programmed by the
user in
6-01 Live Zero Timeout Function
. The signal on one of
the analog inputs is less than 50% of the minimum value
programmed for that input. This condition can be caused by
broken wiring or faulty device sending the signal.
Troubleshooting:
Check connections on all the analog input
terminals. Control card terminals 53 and 54 for
signals, terminal 55 common.
Check that the drive programming match the
analog signal type.
WARNING/ALARM 4, Mains phase loss A phase is missing on
the supply side, or the mains voltage imbalance is too high.
This message also appears for a fault in the input rectifier on
the frequency converter. Options are programmed at
14-12 Function at Mains Imbalance
.
Troubleshooting: Check the supply voltage and supply
currents to the frequency converter.
WARNING/ALARM 7, DC overvoltage
If the intermediate circuit voltage exceeds the limit, the
frequency converter trips after a time.
Troubleshooting:
Extend the ramp time
Activate functions in
WARNING/ALARM 8, DC under voltage
If the intermediate circuit voltage (DC) drops below the
under voltage limit, the frequency converter trips after a
fixed time delay. The time delay varies with unit size.
Troubleshooting:
Check that the supply voltage matches the
frequency converter voltage.
Perform Input voltage test
WARNING/ALARM 9, Inverter overloaded
The frequency converter is about to cut out because of an
overload (too high current for too long). The counter for
electronic, thermal inverter protection gives a warning at
90% and trips at 100%, while giving an alarm. The frequency
converter
cannot
be reset until the counter is below 90%.
The fault is that the frequency converter is overloaded by
more than 100% for too long.
Troubleshooting:
Compare the output current shown on the LCP
with the drive rated current.
Compare the output current shown on the LCP
with measured motor current.
Troubleshooting
VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
77