At power-up
At the first power-up the user is asked to choose preferred
language. Once selected this screen will never be shown
again in the following powerups, but language can still be
changed in
130BB628.10
Select Language
[
0
] English
Setup 1
2.3 Menus
2.3.1 Status
When choosing the [Status] menu it is possible to choose
between the following:
•
Motor Frequency (Hz), par. 16-13;
•
Motor Current (A), par. 16-14;
•
Motor Speed Reference in Percentage (%), par.
16-02;
•
Feedback, par. 16-52;
•
Motor Power (kW) (if
is set to
[1] North America, Motor Power will be shown in
the unit of hp instead of kW), par. 16-10 for kW, par.
16-11 for hp;
•
Custom Readout par. 16-09;
2.3.2 Quick Menu
Allows quick setup of the frequency converter. The most
common VLT HVAC Basic Drive functions can be
programmed here: The [Quick Menu] consists of:
•
Wizard for open loop applications
•
Closed loop set-up wizard
•
Motor set-up
•
Changes made
2.3.3 The FC101 Start-up Wizard for Open
Loop Applications
The built in
wizard
menu guides the installer through the set
up of the frequency converter in a clear and structured
manner in order to setup an open loop application. A open
loop application is here an application with a start signal,
analog reference (voltage or current) and optionally also
relay signals (but no feed back signal from the process
applied).
FC
+24V
DIG IN
DIG IN
DIG IN
DIG IN
COM DIG IN
A OUT / D OUT
A OUT / D OUT
18
19
27
29
42
55
50
53
54
20
12
01
02
03
04
05
06
R2
R1
+
-
0-10V
Start
+10V
A IN
A IN
COM
130BB67
4.10
45
Reference
The wizard will initially be shown after power up until any
parameter has been changed. The wizard can always be
accessed again through the quick menu. Press [OK] to start
the wizard. If [BACK] is pressed, the FC101 will return to the
status screen.
The wizard will initially start up after power up until a
parameter has been changed. The wizard can always be
accessed again through the quick menu. Press [OK] to start
the wizard. If
Cancel
is pressed, the FC101 will return to the
status screen.
130BB629.10
Press OK to start Wizard
Push Back to skip it
Setup 1
How to Programme
VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
13
2
2