8-53 Start Select
Option:
Function:
[2]
Logic AND Activates Start command via the serial communi-
cation port, AND additionally via one of the
digital inputs.
[3]
*
Logic OR
Activates Start command via the serial communi-
cation port OR via one of the digital inputs.
8-54 Reversing Select
Option:
Function:
Select control of the frequency converter reverse
function via the terminals (digital input) and/or
via the serial communication port.
NOTE
This parameter is active only when
is set to [0] Digital and
control word.
[0]
*
Digital
input
Activates Reverse command via a digital input.
[1]
Bus
Activates Reverse command via the serial
communication port.
[2]
Logic AND Activates Reverse command via the serial
communication port, AND additionally via one of
the digital inputs.
[3]
Logic OR
Activates Reverse command via the serial
communication port OR via one of the digital
inputs.
8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the serial communication port.
NOTE
This parameter is active only
when
is set to [0] Digital
and control word.
[0]
Digital
input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial
communication port.
[2]
Logic AND Activates the set-up selection via the serial
communication port, AND additionally via one of
the digital inputs.
[3]
*
Logic OR
Activate the set-up selection via the serial
communication port OR via one of the digital
inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the frequency converter Preset
Reference selection via the terminals (digital
input) and/or via the serial communication port.
[0]
Digital
input
Activates Preset Reference selection via a digital
input.
[1]
Bus
Activates Preset Reference selection via the
serial communication port.
[2]
Logic AND Activates Preset Reference selection via the
serial communication port, AND additionally via
one of the digital inputs.
[3]
*
Logic OR
Activates the Preset Reference selection via the
serial communication port OR via one of the
digital inputs.
3.8.4 8-7* BACnet
8-70 BACnet Device Instance
Range:
Function:
1
*
[0 - 0x3FFFFEUL. ] Enter a unique ID number for the BACnet
device.
8-72 MS/TP Max Masters
Range:
Function:
127.0
*
[0.0 - 127.0 ] Define the address of the master which
holds the highest address in this network.
Decreasing this value optimises polling for
the token.
8-73 MS/TP Max Info Frames
Range:
Function:
1.0
*
[1.0 - 65534.0 ] Define how many info/data frames the
device is allowed to send while holding
the token.
8-74 "I am" Service
Option:
Function:
[0]
*
Send at power-
up
[1]
Continuously
Choose whether the device should send
the "I-Am" service message only at power-
up or continuously with an interval of
approx. 1 min.
8-75 Intialisation Password
Range:
Function:
admin
*
[1 - 1 ] Enter the password needed for execution of
Drive Re-initialisation.
Parameters
VLT HVAC Basic Drive Programming Guide
48
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT HVAC
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive...
Страница 98: ...www danfoss com drives MG18B102 130R0221 MG18B102 Rev 2010 07 21...
Страница 99: ......