3.12 Main Menu - Data Readouts - Group 16
3.12.1 16-0* General Status
16-00 Control Word
Range:
Function:
0
*
[0 - 65535 ] View the Control word sent from the frequency
converter via the serial communication port in
hex code.
Bit number
15 14
13
12
11
10
9 8 7 6 5 4 3 2 1 0
Bit Bit = 0
Bit = 1
00 Preset reference choice lsb
01 Preset reference choice second bit of
preset references
02 DC brake
Ramp
03 Coasting
Enable
04 Quick-stop
Ramp
05 Freeze output
Ramp
06 Ramp stop
Start
07 No function
Reset
08 No function
Jog
09 Ramp 1
Ramp 2
10 Data not valid
Valid
11 Relay_A not active
Relay_A activated
12 Relay_B not active
Relay_B activated
13 Choice of Setup lsb
14 No function
No function
15 No function
Reversing
Table 3.2 Control Word
16-01 Reference [Unit]
Range:
Function:
0.0 ReferenceFeed-
backUnit
*
[-4999.0 - 4999.0
ReferenceFeed-
backUnit]
View the present
reference value applied
on impulse or analog
basis in the unit
resulting from the
configuration selected
in
(Hz).
16-02 Reference [%]
Range:
Function:
0.0 %
*
[-200.0 - 200.0
%]
View the total reference. The total
reference is the sum of digital, analog,
preset, bus, and freeze references.
16-03 Status Word
Range:
Function:
0
*
[0 - 65535 ] View the Status word sent from the frequency
converter via the serial communication port in
hex code.
Bit number
15
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit
Bit = 0
Bit = 1
00
Control not ready
Ready
01
VLT not ready
Ready
02
Coasting
Enable
03
No fault
Trip
04
No warning
Warning
05
Reserved
06
No trip lock
Trip lock
07
No warning
Warning
08
Speed
≠
ref.
Speed = ref.
09
Local control
Bus control
10
Out of range
Frequency OK
11
Not running
Running
12
No function
No function
13
Voltage OK
Above limit
14
Current OK
Above limit
15
Temperature OK
Above limit
Table 3.3 Status Word
16-05 Main Actual Value [%]
Range:
Function:
0.0 %
*
[-200.0 - 200.0 %] View the two-byte word sent with the
Status word to the bus Master
reporting the Main Actual Value.
16-09 Custom Readout
Range:
Function:
0.0 CustomRea-
doutUnit
*
[0.0 - 9999.0
CustomRea-
doutUnit]
View the user-defined
readouts as defined in
,
and
. Custom
Readout
3.12.2 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0.00 kW
*
[0.00 - 1000.00
kW]
Displays DC link power in kW. The
value shown is calculated on the basis
of the actual motor voltage and motor
current.
Parameters
VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
63
3
3