0-32 Custom Readout Max Value
Range:
Function:
100.0 Custom-
ReadoutUnit
*
[0.0 - 999999.99
CustomRea-
doutUnit]
This parameter sets the
max value to be shown
when the speed of the
motor has reached the set
value for
.
0-37 Display Text 1
Range:
Function:
0
*
[0 - 0 ] In this parameter it is possible to write an individual
text string to be read via serial communication.
Only used when running BACnet.
0-38 Display Text 2
Range:
Function:
0
*
[0 - 0 ] In this parameter it is possible to write an individual
text string to be read via serial communication.
Only used when running BACnet.
0-39 Display Text 3
Range:
Function:
0
*
[0 - 0 ] In this parameter it is possible to write an individual
text string to be read via serial communication.
Only used when running BACnet.
3.1.4 0-4* LCP
Enable, disable and password protect individual keys on the
LCP.
0-40 [Hand on] Key on LCP
Option:
Function:
[0]
Disable All Select Disabled [0] to avoid accidental start of the
frequency converter in Hand Mode.
[1]
*
Enable All [Hand on] Key is enabled.
0-42 [Auto on] Key on LCP
Option:
Function:
[0]
Disable All Select Disabled [0] to avoid accidental start of the
frequency converter from LCP.
[1]
*
Enable All [Auto on] Key is enabled.
0-44 [Off / Reset] Key on LCP
Option:
Function:
[0]
Disable All
[1]
*
Enable All
[2]
Enable Reset Only
Off
is disabled.
3.1.5 0-5* Copy / Save
Copy parameter settings between set-ups and to/from the
LCP.
0-50 LCP Copy
Option:
Function:
[0]
*
No copy
[1]
All to LCP
Copies all parameters in all set-ups from the
frequency converter memory to the LCP
memory. For service purposes it is
recommended to copy all parameters to the
LCP after commissioning.
[2]
All from
LCP
Copies all parameters in all set-ups from the
LCP memory to the frequency converter
memory.
[3]
Size indep.
from LCP
Copies only the parameters that are
independent of the motor size. The latter
selection can be used to programme several
frequency converters with the same function
without disturbing motor data which are
already set.
0-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function
[1]
Copy from setup 1 Copy from setup 1 to setup 2.
[2]
Copy from setup 2 Copy from setup 2 to setup 1.
[9]
Copy from Factory
setup
Copy factory setting to programming
setup (chosen in
3.1.6 0-6* Password
0-60 Main Menu Password
Range:
Function:
0
*
[0.0 - 999.0 ] Define the password for access to the Main
Menu via the [Main Menu] key. Setting value to
0 disables the password-function.
Parameters
VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
23