13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[23]
Comparator 1
Use the result of comparator 1 in the
logic rule.
[24]
Comparator 2
Use the result of comparator 2 in the
logic rule.
[25]
Comparator 3
Use the result of comparator 3 in the
logic rule.
[26]
Logic rule 0
Use the result of logic rule 0 in the logic
rule.
[27]
Logic rule 1
Use the result of logic rule 1 in the logic
rule.
[28]
Logic rule 2
Use the result of logic rule 2 in the logic
rule.
[29]
Logic rule 3
Use the result of logic rule 3 in the logic
rule.
[30]
SL Time-out 0
Use the result of timer 0 in the logic
rule.
[31]
SL Time-out 1
Use the result of timer 1 in the logic
rule.
[32]
SL Time-out 2
Use the result of timer 2 in the logic
rule.
[33]
Digital input DI18
Use the value of DI18 in the logic rule
(High = TRUE).
[34]
Digital input DI19
Use the value of DI19 in the logic rule
(High = TRUE).
[35]
Digital input DI27
Use the value of DI27 in the logic rule
(High = TRUE).
[36]
Digital input DI29
Use the value of DI29 in the logic rule
(High = TRUE).
[39]
Start command
This logic rule is TRUE if the frequency
converter is started by any means
(either via digital input, or other).
[40]
Drive stopped
This logic rule is TRUE if the frequency
converter is stopped or coasted by any
means (either via digital input, or other).
[42]
Auto reset trip
This logic rule is TRUE if the frequency
converter is tripped (but not trip-
locked) and an Automatic Reset is
issued.
[50]
Comparator 4
Use the result of comparator 4 in the
logic rule.
[51]
Comparator 5
Use the result of comparator 5 in the
logic rule.
[60]
Logic rule 4
Use the result of logic rule 4 in the logic
rule.
[61]
Logic rule 5
Use the result of logic rule 5 in the logic
rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[70]
SL Time-out 3
Use the result of timer 3 in the logic
rule.
[71]
SL Time-out 4
Use the result of timer 4 in the logic
rule.
[72]
SL Time-out 5
Use the result of timer 5 in the logic
rule.
[73]
SL Time-out 6
Use the result of timer 6 in the logic
rule.
[74]
SL Time-out 7
Use the result of timer 7 in the logic
rule.
[83]
Broken belt
A broken belt condition has been
detected. This function must be
enabled in
[100] Firemode
The frequency converter is operating in
fire mode. See parameter group 24-0*
Fire Mode
13-41 Logic Rule Operator 1
Option:
Function:
[0]
*
Disabled
[1]
AND
[2]
OR
[3]
AND NOT
[4]
OR NOT
[5]
NOT AND
[6]
NOT OR
[7]
NOT AND NOT
[8]
NOT OR NOT
13-42 Logic Rule Boolean 2
Array [6]
Option:
Function:
Select the second boolean (TRUE or
FALSE) input for the selected logic
rule.
See
for
further descriptions of choices and
their functions.
[0]
*
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[16]
Thermal warning
[17]
Mains out of range
Parameters
VLT HVAC Basic Drive Programming Guide
54
MG.18.B1.02 - VLT
®