6-71 Terminal 45 Analog Output
Option:
Function:
[101] Reference
MinRef. - MaxRef.
[102] Feedback
MinFB - MaxFB
[103] Motor current
0 - I
max
[106] Power
0 - P
nom
[139] Bus Control
0 - 100%
6-72 Terminal 45 Digital Output
Option:
Function:
Select the function of
Terminal 45 as a digital
current output. See
also
. See
for
description of the
choices.
[0]
*
No operation
[1]
Control ready
[2]
Drive ready
[3]
Drive ready/remote control
[4]
Standby / no warning
[5]
VLT running
[6]
Running / no warning
[7]
Run in range/no warning
[8]
Run on ref/no warning
[9]
Alarm
[10]
Alarm or warning
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[21]
Thermal warning
[22]
Ready, no thermal warning
[23]
Remote, ready, no thermal warning
[24]
Ready, Voltage OK
[25]
Reverse
[26]
Bus OK
[35]
External Interlock
[36]
Control word bit 11
[45]
Bus Control
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
6-72 Terminal 45 Digital Output
Option:
Function:
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[160] No alarm
[161] Running reverse
[165] Local ref. active
[166] Remote ref. active
[167] Start command activ
[168] Drive in hand mode
[169] Drive in auto mode
[193] Sleep Mode
[194] Broken Belt Function
[196] Fire Mode
[198] Drive Bypass
6-73 Terminal 45 Output Min Scale
Range:
Function:
0.0 %
*
[0.0 - 200.0
%]
Scale for the minimum output (0 or 4mA) of
the analogue signal at Terminal 45. Set the
value to be the percentage of the full range
of the variable selected in
6-74 Terminal 45 Output Max Scale
Range:
Function:
100.0
%
*
[0.0 -
200.0
%]
Scale for the maximum output (20mA) of the
analog signal at Terminal 45. Set the value to be
the percentage of the full range of the variable
selected in
6-71 Terminal 45 Analog Output
.
(mA)
0%
20
0/4
100%
Current
Analogue
output
Min Scale
par. 6-73
Variable
for
output
example:
Power
Analogue
Output
Max Scale
par. 6-74
6-76 Terminal 45 Output Bus Control
Range:
Function:
0.0 %
*
[0.0 - 100.0 %]
Parameters
VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
43
3
3