Closed Loop Set-up Wizard
6-29 Terminal 54 Mode
[1]
Voltage mode
6-25 Terminal 54 High Ref./Feedb. Value
0050
Hz
20-94 PI Integral Time
9999
s
Current
Voltage
This dialog is forced to be set to
[2] Analog in 54
24
25
26
27
28
29
30
31
20-00 Feedback1 source
[2]
Analog in 54
3-10 Preset reference [0]
[1]
0
3-03 Max Reference
[1]
50
3-02 Min Reference
[1]
0
Asynchronous Motor
1-73 Flying Start
[0]
No
1-22 Motor Voltage
0050
V
1-24 Motor current
04.66
A
1-25 Motor nominal speed
1420
RPM
3-41 Ramp 1 ramp-up time
0003
s
3-42 Ramp1 ramp-down time
0003
s
3
4
5
6
7
13
14
15
17
18
18a
20
21
22
23
32
33
34
35
36
37
0-03 Regional Settings
[0]
International
4-12 Motor speed low limit
0016
Hz
4-14 Motor speed high limit
0050
Hz
1
130BB631.10
1-20 Motor Power
1.10
kW
1-23 Motor frequency
0050
Hz
6-22 Terminal 54 Low Current
4 mA
6-24 Terminal 54 Low Ref./Feedb. Value
0016
Hz
6-23 Terminal 54 High Current
20
mA
6-25 Terminal 54 High Ref./Feedb. Value
50
0,01
s
20-81 PI Normal/Inverse Control
[0]
Normal
20-83 PI Start Speed
0
Hz
20-93 PI Proportional Gain
0,01
s
1-29 Automatic Motor Adaption
[1]
Enable
6-20 Terminal 54 Low Voltage
0,07
V
6-24 Terminal 54 Low Ref./Feedb. Value
0
Hz
6-21 Terminal 54 High Voltage
10
V
6-26
Terminal 54 Filter time constant
3-10 Preset reference is the set-point
Please note that Terminal 27 Digital Input (par. 5-12)
has coast inverse as default setting. This means that
AMA can not be performed if there is no 24V to terminal
27 so please connect terminal 12 to terminal 27.
How to Programme
VLT HVAC Basic Drive Programming Guide
16