3.7 Main Menu - Analog In/Out - Group 6
Parameter group for setting up the analog I/O configuration
and the digital output. The frequency converter is equipped
with 2 analog inputs: Terminal 53 and 54. The analog inputs
can freely be allocated to either voltage (0 - 10V) or current
input (0/4 - 20mA)
3.7.1 6-0* Analog I/O Mode
6-00 Live Zero Timeout Time
Range:
Function:
10.0 s
*
[1.0 - 99.0 s]
Enter the time-out time.
6-01 Live Zero Timeout Function
Option:
Function:
Select the time-out function. The function set
in
6-01 Live Zero Timeout Function
will be
activated if the input signal on terminal 53 or
54 is below 50% of the value in
,
or
for a time period defined in
.
[0]
*
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
Ref./Feedback
[RPM]
Analog input
High Ref./
Feedb. Value'
Low Ref./
Feedb. Value'
'Low Voltage'or
'Low Current'
'High Voltage'or
'High Current'
130BA038.13
1 V
5 V
10 V
300
600
900
1200
1500
[V]
150
Par 6-xx
Par 6-xx
Par 6-xx
Par 6-xx
3.7.2 6-1* Analog Input 53
Parameters for configuring the scaling and limits for analog
input 53 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
Function:
0.07 V
*
[0.0 - 10.0
V]
Enter the voltage (V) that corresponds to
6-14 Terminal 53 Low Ref./Feedb. Value
. The
value must be set at >1V in order to
activate
6-01 Live Zero Timeout Function
.
6-11 Terminal 53 High Voltage
Range:
Function:
10.0 V
*
[0.0 - 10.0 V] Enter the voltage (V) that corresponds to
the high reference value (set in par. 6-15).
6-12 Terminal 53 Low Current
Range:
Function:
4.0 mA
*
[0.0 -
20.0 mA]
Enter the low current value. This reference
signal should correspond to the low
reference/feedback value, set in
. The value must be
set at >2mA in order to activate the Live Zero
Time-out Function in
6-13 Terminal 53 High Current
Range:
Function:
20.0 mA
*
[0.0 - 20.0
mA]
Enter the high current value
corresponding to the high reference/
feedback set in
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0.0
*
[-4999.0 - 4999.0 ] Enter the reference or feedback value
that corresponds to the voltage or
current set in par. 6-10/6-12.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
50.0
*
[-4999.0 - 4999.0 ] Enter the reference or feedback value
that corresponds to the voltage or
current set in par. 6-11/6-13.
Parameters
VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
41
3
3