NOTE
In the above, alarms are produced or ignored in accordance
with the selection in
.
24-05 FM Preset Reference
Range:
Function:
0 Hz
*
[-100 - 100 Hz] Enter the required preset reference/set
point as a percentage of the Fire Mode
Max Reference set in Hz.
24-09 FM Alarm Handling
Option:
Function:
[1]
*
Trip, Crit.Alarms
In case of a critical alarm, the frequency
converter will trip and not auto-restart
(Manual Reset).
[2]
Trip, All Alarms/
Test
It is possible to test the operation of Fire
Mode, but all alarm states are activated
normally (Manual Reset).
NOTE
Warranty-affecting alarms. Certain alarms can affect the
lifetime of the frequency converter. Should one of these
ignored alarms occur whilst in Fire Mode, a log of the event
is stored in the Fire Mode Log.
Here the 10 latest events of warranty-affecting alarms, fire
mode activation and fire mode deactivation are stored.
NOTE
The setting in
is disregarded in case of Fire
Mode being active (see parameter group
24-0*, Fire Mode
).
No:
Description
Critical
Alarms
Warranty
Affecting
Alarms
4
Mains ph. Loss
x
7
DC over volt
x
8
DC under volt
x
9
Inverter overloaded
x
13
Over current
x
14
Earth fault
x
16
Short circuit
x
29
Power card temp
x
33
Inrush fault
x
38
Internal fault
x
65
Ctrl. card temp
x
3.16.2 24-1* Drive Bypass
The frequency converter includes a feature, which can be
used to automatically activate an external electro-
mechanical bypass in case of the event of a Fire Mode Coast
(see
The bypass will switch the motor to operation direct on line.
The external bypass is activated by means of one of the
digital outputs or relays in the frequency converter, when
programmed in parameter group 5-3* or parameter group
5-4*.
NOTE
The Drive Bypass cannot be deactivated if in Fire Mode. It
can be deactivated only by either removing the Fire Mode
command signal or the power supply to the frequency
converter!
When the Drive Bypass function is activated, the display on
the LCP will show the status message Drive Bypass. This
message has a higher priority than the Fire Mode status
messages. When the automatic Drive Bypass function is
enabled, it will cut in the external bypass according to the
below sequence:
130BA546.10
Operation
Alarm
Relay
"Bypass"
On delay (P5-41)
Speed
ON
OFF
Auto Resets
Auto Reset Disabled
Bypass
Delay
Timer
P24-11
Alarm
Status can be read in the Extended Status Word 2, bit
number 24.
24-10 Drive Bypass Function
Option:
Function:
This parameter determines, what circum-
stances will activate the Drive Bypass
Function:
[0]
*
Disabled
[2]
Enabled (Fire
Mode only)
The Bypass Function will operate at Trip at
Critical Alarms, Coast or Bypass Delay Timer
if the timer expires before reset attempts
have completed.
Parameters
VLT HVAC Basic Drive Programming Guide
72
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT HVAC
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive...
Страница 98: ...www danfoss com drives MG18B102 130R0221 MG18B102 Rev 2010 07 21...
Страница 99: ......