2 How to Programme
2.1 Programming with MCT-10 Setup
software
The frequency converter can be programmed from a PC via
RS-485 COM port by installing the MCT-10 Setup software.
This software can either be ordered using code number
130B1000 or downloaded from the Danfoss Web site: http://
www.danfoss.com/BusinessAreas/DrivesSolutions/Software-
download/ Please refer to manual MG.10.RX.YY.
2.2 Local Control Panel (LCP)
The following instructions are valid for the FC101 LCP. The
LCP is divided into four functional sections:
A. Alphanumeric display.
B. Menu key.
C. Navigation keys and indicator lights (LEDs).
D. Operation keys and indicator lights (LEDs).
Ba
ck
Com
1-20 Motor Power
[2] 0.12kW-0.16HP
Setup 1
A
B
1
12
13
14
15
11
11
10
9
8
7
6
5
4
3
2
C
D
Status
Main
Menu
Quick
Menu
Hand
On
OK
Menu
Off
Reset
Auto
On
Alarm
Warn
On
130BB765.10
A. Alpha Numeric Display
The LCD-display is back-lit with 2 alpha-numeric lines. All
data is displayed on the LCP.
A number of information can be read from the display:
1
Parameter number and name.
2
Parameter value.
3
Set-up number shows the active set-up and the edit set-up.
If the same set-up acts as both active and edit set-up, only
that set-up number is shown (factory setting). When active
and edit set-up differ, both numbers are shown in the
display (Setup 12). The number flashing, indicates the edit
set-up.
4
Motor direction is shown to the bottom left of the display –
indicated by a small arrow pointing either clockwise or
counterclockwise.
5
The triangle indicates if the LCP is in status, quick menu or
main menu.
B. Menu Key
Use the menu key to select between status, quick menu or
main menu.
C. Navigation keys and indicator lights (LEDs)
6 Com led: Flashes when bus communication is communicating.
7 Green LED/On: Control section is working.
8 Yellow LED/Warn.: Indicates a warning.
9 Flashing Red LED/Alarm: Indicates an alarm.
10 [Back]: For moving to the previous step or layer in the
navigation structure
11 Arrows [
▲
] [
▼
]: For maneuvering between parameter groups,
parameters and within parameters. Can also be used for
setting local reference.
12 [OK]: For selecting a parameter and for accepting changes to
parameter settings
D. Operation keys and indicator lights (LEDs)
13 [Hand on]: Starts the motor and enables control of the
frequency converter via the LCP.
NOTE
Please note that terminal 27 Digital Input
(
5-12 Terminal 27 Digital Input
) has coast inverse as
default setting. This means that [Hand On] will not
start the motor if there is no 24V to terminal 27, so
please connect terminal 12 to terminal 27.
14 [Off/Reset]: Stops the motor (off). If in alarm mode the alarm
will be reset.
15 [Auto on]: Frequency converter is controlled either via control
terminals or serial communication.
How to Programme
VLT HVAC Basic Drive Programming Guide
12
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
2
2