22-46 Maximum Boost Time
Range:
Function:
60 s
*
[0 - 600
s]
Only to be used if
is set
for Closed Loop and the integrated PI controller is
used for controlling the pressure.
Set the maximum time for which boost mode will
be allowed. If the set time is exceeded, Sleep
Mode will be entered, not waiting for the set
boost pressure to be reached.
22-47 Sleep Speed [Hz]
Range:
Function:
0.0 s
*
[0.0 - 400.0 s] Set the speed below which the frequency
converter will go into Sleep Mode.
3.15.2 22-6* Broken Belt Detection
The Broken Belt Detection can be used in both closed and
open loop systems for pumps and fans. If the estimated
motor torque (current) is below the broken belt torque
(current) value (
) and the frequency
converter output frequency is above or equal to 15Hz,
is performed
22-60 Broken Belt Function
Selects the action to be performed if the Broken Belt condition is
detected.
Option:
Function:
[0]
*
Off
[1]
Warning The frequency converter will continue to run, but
activate a Broken Belt Warning [W95]. A drive
digital output or a serial communication bus can
communicate a warning to other equipment.
[2]
Trip
The frequency converter will stop running and
activate a Broken Belt alarm [A 95]. A drive digital
output or a serial communication bus can
communicate an alarm to other equipment.
NOTE
Do not set
, to [13] Infinite auto reset, when
is set to [2] Trip. Doing so will
cause the frequency converter to continuously cycle
between running and stopping when a broken belt
condition is detected.
NOTE
If the frequency converter is equipped with a constant speed
bypass with an automatic bypass function that starts the
bypass if the frequency converter experiences a persistent
alarm condition, be sure to disable the bypass’s automatic
bypass function, if [2] Trip is selected as the Broken Belt
Function.
22-61 Broken Belt Torque
Range:
Function:
10 %
*
[5 - 100 %] Sets the broken belt torque as a percentage
of the rated motor torque.
22-62 Broken Belt Delay
Range:
Function:
10 s
*
[0 - 600 s] Sets the time for which the Broken Belt
conditions must be active before carrying out
the action selected in
Parameters
VLT HVAC Basic Drive Programming Guide
70
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT HVAC
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive...
Страница 98: ...www danfoss com drives MG18B102 130R0221 MG18B102 Rev 2010 07 21...
Страница 99: ......