5-12 Terminal 27 Digital Input
Parameter for configuring the input function on input terminal 27.
Option:
Function:
[60]
Counter A (up)
[61]
Counter A (down)
[62]
Reset Counter A
[63]
Counter B (up)
[64]
Counter B (down)
[65]
Reset Counter B
5-13 Terminal 29 Digital Input
Parameter for configuring the input function on input terminal 29.
Option:
Function:
[0]
No operation
[1]
Reset
[2]
Coast inverse
[3]
Coast and reset inverse
[4]
Quick Stop inverse
[5]
DC-brake inverse
[6]
Stop inverse
[7]
External Interlock
[8]
Start
[9]
Latched start
[10]
Reversing
[11]
Start reversing
[14]
*
Jog
[16]
Preset ref bit 0
[17]
Preset ref bit 1
[18]
Preset ref bit 2
[19]
Freeze reference
[20]
Freeze output
[21]
Speed up
[22]
Speed down
[23]
Set-up select bit 0
[34]
Ramp bit 0
[37]
Fire mode
[52]
Run permissive
[53]
Hand Start
[54]
Auto start
[60]
Counter A (up)
[61]
Counter A (down)
[62]
Reset Counter A
[63]
Counter B (up)
[64]
Counter B (down)
[65]
Reset Counter B
3.6.3 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
Function:
[0]
*
No operation
Default for both relays
[1]
Control ready
Control board receives supply voltage.
[2]
Drive ready
Frequency converter is ready for
operation and applies supply signal on
control board.
[3]
Drive ready/
remote control
Frequency converter is ready for
operation in Auto On-mode.
[4]
Standby / no
warning
Frequency converter is ready for
operation. No start or stop command is
given. No warnings are present.
[5]
VLT running
Motor is running.
[6]
Running / no
warning
Motor runs, and no warning are present.
[7]
Run in range/no
warning
Motor runs within programmed current
ranges, see
and
. No warnings
are present.
[8]
Run on ref/no
warning
Motor runs at reference speed and with
no warnings.
[9]
Alarm
An alarm activates output.
[10]
Alarm or
warning
An alarm or warning activates output.
[12]
Out of current
range
Motor current is outside range set in
and
[13]
Below current,
low
Motor current is lower than set in
[14]
Above current,
high
Motor current is higher than set in
[21]
Thermal warning The thermal warning turns on when the
temperature exeeds the limit in motor,
frequency converter or thermistor.
[22]
Ready, no
thermal warning
Frequency converter is ready for
operation and no over-temperature
warning is present.
[23]
Remote, ready,
no thermal
warning
Frequency converter is ready for
operation in Auto mode, and no over-
temperature warning is present.
Parameters
VLT HVAC Basic Drive Programming Guide
38
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark