3 Parameters
3.1 Main Menu - Operation and Display -
Group 0
Parameters related to the fundamental functions of the
frequency converter, function of the LCP buttons and config-
uration of the LCP display.
3.1.1 0-0* Basic Settings
0-01 Language
Option:
Function:
Defines the language to be used in the display.
[0]
*
English
[1]
Deutsch
[2]
Francais
[3]
Dansk
[4]
Spanish
[5]
Italiano
[28]
Bras.port
[255] No Text
0-03 Regional Settings
Option:
Function:
This parameter cannot be adjusted while the
motor is running. In order to meet the needs for
different default settings in different parts of the
world,
is implemented in
the frequency converter. The selected setting
influences the default setting of the motor
nominal frequency.
[0]
*
Interna-
tional
Sets default value of
[50Hz].
[1]
North
America
Sets the default value of
to
60Hz.
0-04 Operating State at Power-up
Option:
Function:
Select the operating mode upon reconnection of
the frequency converter to mains voltage after
power down when operating in Hand (local)
mode.
[0]
*
Resume
Resumes operation of the frequency converter
maintaining the same local reference and the
same start/stop condition (applied by [Hand On]/
[Off] on the LCP or Hand Start via a digital input
as before the frequency converter was powered
down.
0-04 Operating State at Power-up
Option:
Function:
[1]
Forced
stop,
ref=old
Uses saved reference [1] to stop the frequency
converter but at the same time retain the local
speed reference in memory prior to power down.
After mains voltage is reconnected and after
receiving a start command (using the LCP [Hand
On] button or Hand Start command via a digital
input) the frequency converter restarts and
operates at the retained speed reference.
0-06 GridType
Option:
Function:
Select the grid type of the supply
voltage/frequency.
NOTE
Not all choices are supported in
all power sizes.
IT grid is a supply mains, where there
are no connections to ground.
Delta is a supply mains where the
secondary part of the transformer is
delta connected and one phase is
connected to ground.
[0]
200-240V/50Hz/IT-
grid
[1]
200-240V/50Hz/Delta
[2]
200-240V/50Hz
[10]
380-440V/50Hz/IT-
grid
[11]
380-440V/50Hz/Delta
[12]
380-440V/50Hz
[20]
440-480V/50Hz/IT-
grid
[21]
440-480V/50Hz/Delta
[22]
440-480V/50Hz
[30]
525-600V/50Hz/IT-
grid
[31]
525-600V/50Hz/Delta
[32]
525-600V/50Hz
[100] 200-240V/60Hz/IT-
grid
[101] 200-240V/60Hz/Delta
[102] 200-240V/60Hz
[110] 380-440V/60Hz/IT-
grid
[111] 380-440V/60Hz/Delta
[112] 380-440V/60Hz
Parameters
VLT HVAC Basic Drive Programming Guide
20
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
3
3