1-84 Precise Stop Counter Value
Range:
Function:
100000
*
[0 - 999999999 ] Enter the counter value to be used
in the integrated precise stop
function,
1-83 Precise Stop Function
.
The maximum permissible frequency
at terminal 29 or 33 is 110kHz.
Not used for selection [0] and [3] in
1-83 Precise Stop Function
1-85 Precise Stop Speed Compensation Delay
Range:
Function:
10 ms
*
[0 - 100
ms]
Enter the delay time for sensors, PLCs, etc.
for use in
1-83 Precise Stop Function
. In
speed compensated stop mode, the delay
time at different frequencies has a major
influence on the stop function.
Not used for selection [0], [1] and [2] in
1-83 Precise Stop Function
3.3.9 1-9* Motor Temperature
1-90 Motor Thermal Protection
Option:
Function:
Thermal motor protection can be
implemented using a range of techniques:
•
Via a PTC sensor in the motor
windings connected to one of the
analog or digital inputs
(
1-93 Thermistor Source
). See
3.3.10.1 PTC Thermistor Connection
.
•
Via a KTY sensor in the motor
winding connected to an analog
input (
1-96 KTY Thermistor Resource
).
See
3.3.10.2 KTY Sensor Connection
.
•
Via calculation (ETR = Electronic
Thermal Relay) of the thermal load,
based on the actual load and time.
The calculated thermal load is
compared with the rated motor
current I
M,N
and the rated motor
frequency f
M,N
. See
3.3.10.3 ETR
and
3.3.10.4 ATEX ETR
.
•
Via a mechanical thermal switch
(Klixon type). See
3.3.10.5 Klixon
.
For the North American market: The ETR
functions provide class 20 motor overload
protection in accordance with NEC.
1-90 Motor Thermal Protection
Option:
Function:
[0]
*
No
protection
Continuously overloaded motor, when no
warning or trip of the Adjustable frequency
drive is required.
[1]
Thermistor
warning
Activates a warning when the connected
thermistor or KTY sensor in the motor reacts
in the event of motor overtemperature.
[2]
Thermistor
trip
Stops (trips) Adjustable frequency drive when
connected thermistor or KTY sensor in the
motor reacts in the event of motor overtem-
perature.
The thermistor cut-out value must be > 3
k
Ω
.
Integrate a thermistor (PTC sensor) in the
motor for winding protection.
[3]
ETR warning
1
Calculates the load when set-up 1 is active
and activates a warning on the display when
the motor is overloaded. Program a warning
signal via one of the digital outputs.
[4]
ETR trip 1
Calculates the load when set-up 1 is active
and stops (trips) Adjustable frequency drive
when the motor is overloaded. Program a
warning signal via one of the digital outputs.
The signal appears in the event of a warning
and if the Adjustable frequency drive trips
(thermal warning).
[5]
ETR warning
2
[6]
ETR trip 2
[7]
ETR warning
3
[8]
ETR trip 3
[9]
ETR warning
4
[10] ETR trip 4
[20] ATEX ETR
Activates the thermal monitoring function for
Ex-e motors for ATEX. Enables
1-94 ATEX ETR
cur.lim. speed reduction
,
1-98 ATEX ETR
interpol. points freq.
and
1-99 ATEX ETR
interpol points current
.
[21] Advanced
ETR
NOTE!
If [20] is selected, follow the instructions exactly as
described in the dedicated chapter in the VLT
AutomationDrive design guide and the instructions given
by the motor manufacturer.
Parameter Descriptions
FC 300 Programming Guide
3-24