13-10 Comparator Operand
Array [6]
Option:
Function:
[151] SL digital output
B
SL digital output B
[151] Use the result of
the SLC output B.
[152] SL digital output
C
SL digital output C
[152] Use the result
of the SLC output C.
[153] SL digital output
D
SL digital output D
[153] Use the result
of the SLC output D.
[154] SL digital output
E
SL digital output E
[154] Use the result of
the SLC output E.
[155] SL digital output
F
SL digital output F
[155] Use the result of
the SLC output F.
[160] Relay 1
Relay 1
[160] Relay 1 is active
[161] Relay 2
Relay 2
[161] Relay 2 is active
[180] Local ref. active
Local ref. active
[180] High when
3-13 Reference Site
= [2] Local or when
3-13 Reference Site
is [0] Linked to hand
auto, at the same time as the LCP is in
hand on mode.
[181] Remote ref.
active
Remote ref. active
[181] High when
3-13 Reference Site
= [1] Remote or [0]
Linked to hand/auto, while the LCP is in
auto on mode.
[182] Start command
Start command
[182] High when there is
an active start command and no stop
command.
[183] Drive stopped
Drive stopped
[183] A stop command
(Jog, Stop, Qstop, Coast) is issued – and
not from the SLC itself.
[185] Drive in hand
mode
Drive in hand mode
[185] High when the
Adjustable frequency drive is in hand
mode.
[186] Drive in auto
mode
Drive in auto mode
[186] High when the
Adjustable frequency drive is in auto
mode.
[187] Start command
given
[190] Digital input x30
2
[191] Digital input x30
3
[192] Digital input x30
4
[193] Digital input x46
1
[194] Digital input x46
2
13-10 Comparator Operand
Array [6]
Option:
Function:
[195] Digital input x46
3
[196] Digital input x46
4
[197] Digital input x46
5
[198] Digital input x46
6
[199] Digital input x46
7
13-11 Comparator Operator
Array [6]
Option:
Function:
Select the operator to be used in the
comparison. This is an array parameter
containing comparator operators 0 to 5.
[0]
<
Select < [0] for the result of the evaluation to
be TRUE, when the variable selected in
13-10 Comparator Operand
is smaller than the
fixed value in
13-12 Comparator Value
. The
result will be FALSE, if the variable selected in
13-10 Comparator Operand
is greater than the
fixed value in
13-12 Comparator Value
.
[1]
*
≈ (equal)
Select ≈ [1] for the result of the evaluation to
be TRUE, when the variable selected in
13-10 Comparator Operand
is approximately
equal to the fixed value in
13-12 Comparator
Value
.
[2]
>
Select > [2] for the inverse logic of option <
[0].
[5]
TRUE longer
than..
[6]
FALSE
longer
than..
[7]
TRUE
shorter
than..
[8]
FALSE
shorter
than..
Parameter Descriptions
FC 300 Programming Guide
3-116