14-22 Operation Mode
Option:
Function:
130BA097.12
FC 302
FC 301
FC 301 &
FC 302
13
12
18
37
32
27
19
29
33 20
50
39 42
54
53
55
19
18
12 13
20
33
27
32
Select
Initialization
[2] to reset all parameter
values to default settings, except for
15-03 Power Up's
,
15-04 Over Temp's
, and
15-05 Over Volt's
. The Adjustable frequency
drive will reset during the next power-up.
14-22 Operation Mode
will also revert to the
default setting
Normal operation
[0].
[0]
*
Normal
operation
[1]
Control
card test
[2]
Initialisation
[3]
Boot mode
14-24 Trip Delay at Current Limit
Range:
Function:
60 s
*
[0 - 60
s]
Enter the current limit trip delay in seconds.
When the output current reaches the current
limit (
4-18 Current Limit
), a warning is triggered.
When the current limit warning has been contin-
uously present for the period specified in this
parameter, the Adjustable frequency drive trips.
Disable the trip delay by setting the parameter
to 60 sec. = OFF. Thermal monitoring of the
Adjustable frequency drive will still remain active.
14-25 Trip Delay at Torque Limit
Range:
Function:
60 s
*
[0 -
60 s]
Enter the torque limit trip delay in seconds.
When the output torque reaches the torque
limits (
4-16 Torque Limit Motor Mode
and
4-17 Torque Limit Generator Mode
), a warning is
triggered. When the torque limit warning has
been continuously present for the period
specified in this parameter, the Adjustable
frequency drive trips. Disable the trip delay by
14-25 Trip Delay at Torque Limit
Range:
Function:
setting the parameter to 60 sec. = OFF. Thermal
monitoring of the Adjustable frequency drive will
still remain active.
14-26 Trip Delay at Inverter Fault
Range:
Function:
Application
dependent
*
[0 -
35 s]
When the Adjustable frequency drive
detects an overvoltage in the set time,
tripping will be effected after the set
time.
If value = 0,
protection mode
is disabled
NOTE!
It is recommended to disable
protection mode
in hoisting
applications.
0. s
*
[0 -
35 s]
When the Adjustable frequency drive
detects an overvoltage in the set time,
tripping will be effected after the set
time.
If value = 0,
protection mode
is disabled
NOTE!
It is recommended to disable
protection mode
in hoisting
applications.
14-29 Service Code
Range:
Function:
0
*
[-2147483647 - 2147483647 ]
For internal service only.
3.15.3 14-3* Current Limit Control
The Adjustable frequency drive features an integral current
limit controller which is activated when the motor current,
and thus the torque, is higher than the torque limits set in
4-16 Torque Limit Motor Mode
and
4-17 Torque Limit
Generator Mode
.
When the current limit is reached during motor operation
or regenerative operation, the Adjustable frequency drive
will try to reduce torque below the preset torque limits as
quickly as possible without losing control of the motor.
While the current control is active, the Adjustable
frequency drive can only be stopped by setting a digital
input to
Coast inverse
[2] or
Coast and reset inv.
[3]. Any
signal on terminals 18 to 33 will not be active until
theAdjustable frequency drive is no longer near the
current limit.
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®